| 2014-03-28 15:17:35 | PLUMBING PLAN REVIEW |
| | PERMIT: 14031087 |
| | ADD: 844 BRADLEY ST |
| | CONT: DENNIS PORCELAIN ENT |
| | TEL: (561)248-6839 |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | 1ST REVIEW |
| | DATE: FRIDAY MARCH 28/2014 |
| | ACTION: PLUMBING REVIEW: PROVISO |
| | 1) A SEPARATE PLUMBING PERMIT WILL BE REQUIRED FOR THE |
| | RENOVATION OF THE BATHROOM, REMOVAL OF FIXTURES, STOPS |
| | AND OR VALVES AND NEW SHOWER ENCLOSURE. |
| | 2) P2503.6 SHOWER LINER TEST. |
| | WHERE SHOWER FLOORS AND RECEPTORS ARE MADE WATER TIGHT |
| | BY THE APPLICATION OF MATERIALS REQUIRED BY SECTION |
| | P2709.2, THE COMPLETED LINER INSTALLATION SHALL BE |
| | TESTED. THE PIPE FROM THE SHOWER DRAIN SHALL BE PLUGGED |
| | WATER TIGHT FOR THE TEST. THE FLOOR AND RECEPTOR AREA |
| | SHALL BE FILLED WITH POTABLE WATER TO A DEPTH OF NOT |
| | LESS THAN 2 INCHES (51 MM) MEASURED AT THE THRESHOLD. |
| | WHERE A THRESHOLD OF AT LEAST 2 INCHES HIGH DOES NOT |
| | EXIST, A TEMPORARY THRESHOLD SHALL BE CONSTRUCTED TO |
| | RETAIN THE TEST WATER IN THE LINED FLOOR OR RECEPTOR |
| | AREA TO A LEVEL NOT LESS THAN 2 INCHES DEEP MEASURED AT |
| | THE THRESHOLD. THE WATER SHALL BE RETAINED FOR A TEST |
| | PERIOD OF NOT LESS THAN 15 MINUTES AND THERE SHALL BE |
| | NO EVIDENCE OF LEAKAGE. |
| | 3) P2709.2 LINING REQUIRED. |
| | THE ADJOINING WALLS AND FLOOR FRAMING ENCLOSING ON-SITE |
| | BUILT-UP SHOWER RECEPTORS SHALL BE LINED WITH ONE OF |
| | THE FOLLOWING MATERIALS: |
| | 1. SHEET LEAD, |
| | 2. SHEET COPPER, |
| | 3. PLASTIC LINER MATERIAL THAT COMPLIES WITH ASTM D |
| | 4068 OR ASTM D 4551, |
| | 4. HOT MOPPING IN ACCORDANCE WITH SECTION P2709.2.3 OR |
| | 5. SHEET-APPLIED LOAD-BEARING, BONDED WATERPROOF |
| | MEMBRANES THAT COMPLY WITH ANSI A118.10. |
| | THE LINING MATERIAL SHALL EXTEND NOT LESS THAN 3 INCHES |
| | (76 MM) BEYOND OR AROUND THE ROUGH JAMBS AND NOT LESS |
| | THAN 3 INCHES (76 MM) ABOVE FINISHED THRESHOLDS. |
| | SHEET-APPLIED LOAD BEARING, BONDED WATERPROOF MEMBRANES |
| | SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER?S |
| | INSTALLATION INSTRUCTIONS. |
| | EXCEPTIONS: |
| | 1. FLOOR SURFACES UNDER SHOWERHEADS PROVIDED FOR |
| | RINSING LAID DIRECTLY ON THE GROUND. |
| | 2. SHOWER COMPARTMENTS WHERE THE FINISHED SHOWER DRAIN |
| | IS DEPRESSED A MINIMUM OF 2 INCHES (51 MM) BELOW THE |
| | SURROUNDING FINISHED FLOOR ON THE FIRST FLOOR LEVEL AND |
| | THE SHOWER RECESS IS POURED INTEGRALLY WITH THE |
| | ADJOINING FLOOR. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO/ SENIOR COMMERCIAL COMBINATION |
| | PLANS EXAMINER |