Plan Review Notes
Plan Review Notes For Permit 14031056
Permit Number 14031056
Review Stop E
Sequence Number 3
Notes
Date Text
2015-07-31 11:03:23PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. PLEASE NOTE THAT RESUBMITTING INSTRUCTIONS WERE
 PROVIDED YOU WITH THE SECOND ELECTRICAL DENIAL. THOSE
 DIRECTIONS HAVE NOT BEEN FOLLOWED. PLEASE DO SO THIS
 TIME AROUND.
 2. THE RISER DIAGRAM REFLECTS TWO PANEL, THE LOCATION
 OF WHICH ARE NOT INDICATED ON THE PLANS.
 3. A CIRCUIT DIRECTORY AS PER NEC 408.4 SHALL BE
 PROVIDE FOR THE NEW 60 AMP PANEL INDICATED ON THE
 RISER.
 4. YOU SHALL ALSO PROVIDE LOAD CALC FOR THE NEW 60 AMP
 PANEL.
 5. THE RISER SHOWS THE NEW 60 AMP PANEL BEING SERVED
 FROM DISC A, BUT PANEL A DOES NOT REFLECT AN OCPD FOR
 THE NEW PANEL.
 6. YOU SHALL SUBMIT A WHOLE HOUSE FLOOR PLAN INDICATING
 THE RELATION OF THE NEW ADDITION TO THE EXISTING. SHOW
 ON IT THE LOCATION OF THE FPL SERVICE METER, MAIN
 DISCONNECT, ALL ELECTRICAL PANELS AND EXISTING SMOKE
 DETECTORS.
 7. THE ELECTRICAL GFI OUTLET FOR THE HYDROMASSAGE TUB
 SHALL BE IN AN ACCESSIBLE LOCATION AS PER NEC 680.71.
 FURTHERMORE ALL THE ELECTRICAL COMPONENTS SHALL BE
 ACCESSIBLE WITH DAMAGING THE WALLS AS PER NEC 680.73.
 8. ALL REPLACEMENT RECEPTACLES SHALL BE
 TAMPER-RESISTANT AND COMPLY WITH NEC 406.3 (D)(1) TO
 (D)(3)
 9. ALL OUTDOOR RECEPTACLES SHALL BE RATED AS WEATHER
 RESISTANT "WR".
 10 ALL OUTLETS INSTALLED IN CEILING SHALL BE RATED TO
 SUPPORT 50# AS PER NEC 314.27
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  