2014-04-24 11:53:54FAILED FIRST ELECTRICAL REVIEW AS FOLLOWS:
 1. THE MECHANICAL PLAN SHOWS A NEW MINI-SPLIT A/C
 SYSTEM THAT IS NOT REFLECTED ON THE ELECTRICAL PLANS.
 2. YOU SHALL INCLUDE THIS UNIT ALONG WILL ALL
 ASSOCIATED ELECTRIC, DISCONNECT ETC. ON THE ELECTRICAL
 PLAN.
 3. IF THIS UNIT IS TO BE INSIDE THE ATTIC, ADDITIONAL
 REQUIREMENTS WILL APPLY. JUST TO MENTION A FEW: PROPER
 LIGHTING, A SERVICE OUTLET AND A PERMANENT LADDER
 4. PROVIDE A PANEL SCHEDULE AND LOAD CALCS TO VERIFY
 AMPLE CAPACITY FOR THE ADDED LOAD.
 5. FOR CONVENIENCE AND ENERGY CONSERVATION ONLY, THREE
 WAY SWITCHING SHOULD BE PROVIDE AT THE HALLWAY AND
 MULTIPLE ENTRANCES TO THE BEDROOM.
  