Plan Review Notes
Plan Review Notes For Permit 14031056
Permit Number 14031056
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-03 10:03:172010 FBC
 ADDITION OF MASTER SUITE
  
 DENIED BY BUILDING
  
 1) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN IS REQUIRED ON THE PLANS. CITY AMENDMENTS
 107.2.1
  
 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE
 ADDITION AS REQUIRED BY THE 2010 FBC ENERGY
 CONSERVATION SECTION 40.2. THE FORMS ARE REQUIRED TO BE
 SIGNED AND DATED BY THE PREPARER AND OWNER/AGENT.
  
 3) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THE
 STRUCTURE IS LOCATED IN A 170 MPH VULT WIND SPEED AND
 THE DEFAULT EXPOSURE CATEGORY IS "C". CITY AMENDMENTS
 107.5.3
  
 4) SPECIFY THE REQUIRED WIND DESIGN PRESSURES FOR THE
 EXTERIOR OPENINGS ON THE PLANS. CITY AMENDMENTS 107.5.3
  
 5) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 6) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 GRACE WATER / ICE SHIELD ROOFING UNDERLAYMENT THAT IS
 SPECIFIED ON THE PLANS. DCA RULE 9N-3
  
 7) THE WINDOW SCHEDULE ON SHEET A1 SPECIFIES THAT ALL
 OF THE WINDOWS ARE SINGLE HUNG. THE PRODUCT APPROVALS
 THAT WERE SUBMITTED ARE FOR HORIZONTAL SLIDING WINDOWS.
 PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 8) THE WINDOW SCHEDULE ON SHEET A1 SPECIFIES PGT
 WINGUARD WINDOWS AND DOORS AND LAWSON PRODUCT APPROVALS
 WERE SUBMITTED. THE DESIGNER DID NOT STATE THAT AN
 APPROVED EQUAL COULD BE USED ON THE PLANS. PLEASE
 CORRECT. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]