| Permit Number |
14031030 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-18 10:29:37 | PLUMBING PLAN REVIEW | | | PERMIT:14031030 | | | ADD: 6651N JOG RD | | | CONT: | | | TEL: (561 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE:FRI. APRIL 18/2014 | | | ACTION: DENIED | | | | | | 1) SHEET 200-PL-000 PIPE EQUIPMENT & MATERIAL NOTES: | | | NOTE # 4, SANITARY, STORM DRAIN PIPE AND VENT PIPING | | | UNDERGROUND & ABOVE GROUND WITHIN FRAME WALLS. BLOCK | | | MASONRY OR PIPE CHASE SHALL BE TYPE DWV, TO ASTM D2665, | | | D2949 AND D3034. PLEASE REVIEW 2010 FBC-P TABLE 702.1 | | | ABOVE GROUND DRAINAGE AND VENT AND TABLE 702.2 BOTH | | | REQUIRED DMV TO MEET STANDARD ASTM B75, ASTM B88, ASTM | | | B 251 OR ASTM B 306. THE USE OF DWV AS STORM SUBSOIL | | | DRAIN PIPE WITHIN THE BUILDING IS NOT ALLOWED SEE TABLE | | | 1102.5. | | | | | | 2) SHEET 200-PL-900 ELEVATION 50'-0" REVISION # 3 | | | YELLOW BOX WITH COMMENT WHERE WE ROUTE THIS VENT PIPE | | | APPEARS THAT THE DESIGNER OF RECORD STILL HAS SOME WORK | | | TO DO BEFORE THIS PAGE IS SUBMITTED TO THE BUILDING | | | DEPARTMENT. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|