| Date |
Text |
| 2014-05-02 10:50:32 | BUILDING PLAN REVIEW |
| | PERMIT: 14030980 |
| | ADD: 3421 N AUSTRALIAN AVE |
| | CONT: TBD |
| | TEL: (561)502-1957 SOPHIA BARRETT |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2NDREVIEW |
| | DATE: FRI. MAY 02/ 2014 |
| | ACTION: DENIED |
| | |
| | DEFINTIONS: |
| | 313.2.1 FAMILY DAY CARE HOME. |
| | A FAMILY DAY CARE HOME IS A DAY CARE HOME IN WHICH MORE |
| | THAN THREE BUT FEWER THAN SEVEN CLIENTS RECEIVE CARE, |
| | MAINTENANCE AND SUPERVISION BY OTHER THAN THEIR |
| | RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS |
| | PER DAY WITH NO MORE THAN TWO CLIENTS INCAPABLE OF |
| | SELF-PRESERVATION. |
| | |
| | 313.2.2 GROUP DAY CARE HOME. |
| | A GROUP DAY CARE HOME IS A DAY-CARE HOME IN WHICH AT |
| | LEAST SEVEN BUT NOT MORE THAN 12 CLIENTS RECEIVE CARE, |
| | MAINTENANCE, AND SUPERVISION BY OTHER THAN THEIR |
| | RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS |
| | PER DAY WITH NO MORE THAN THREE CLIENTS INCAPABLE OF |
| | SELF-PRESERVATION. |
| | |
| | THIS REVIEW IS BEING COMPLETED AS A GROUP HOME DAY |
| | CARE. |
| | |
| | 1) 2ND REQUEST. PLEASE PROVIDE THE AGE OF THE CHILDREN |
| | THAT WILL BE UNDER YOUR SUPERVISION AND THE AMOUNT OF |
| | CLIENTS THAT WOULD BE INCAPABLE OF SELF-PRESERVATION. |
| | FBC-B 313.2.2. |
| | |
| | 2) NOTE, RESPONSE INDICATES THE CHILDREN WILL USE ONE |
| | OF THE TWO RESTROOMS, DOES THAT MEAN IF ONE IS OCCUPIED |
| | THEY WILL BE ABLE TO USE THE OTHER? IF THEY USE THE |
| | BATHROOM IN THE BEDROOM ARE THE DOORS LOCKABLE? 436.3 |
| | BATHROOM DOORS. |
| | EVERY BATHROOM DOOR LOCK SHALL BE DESIGNED TO PERMIT |
| | OPENING OF THE LOCKED DOOR FROM THE OUTSIDE IN AN |
| | EMERGENCY. THE OPENING DEVICE SHALL BE READILY |
| | ACCESSIBLE TO THE STAFF. |
| | THE PLANS HAVE A CIRCLED AREA, IS THIS AREA (OFFICE) |
| | THE AREA OF THE GROUP DAY CARE HOME, IF SO WHERE ARE |
| | THE BATHROOM FACILITIES? |
| | |
| | 3)2ND REQUEST, PLEASE PROVIDE THE SIZE OF THE WINDOW IN |
| | THE GARAGE, 2010 FBC-B1037.8.3 |
| | IN GROUP DAY CARE HOMES, EVERY ROOM USED FOR SLEEPING, |
| | LIVING OR DINING PURPOSES SHALL HAVE AT LEAST TWO MEANS |
| | OF ESCAPE, AT LEAST ONE OF WHICH SHALL BE A DOOR OR |
| | STAIRWAY THAT PROVIDES A MEANS OF NONOBSTRUCTED TRAVEL |
| | TO THE OUTSIDE OF THE BUILDING AT STREET OR GROUND |
| | LEVEL. THE SECOND MEANS OF ESCAPE MAY BE A WINDOW. |
| | PROVIDE THE OVER ALL WINDOW DIMENSIONS AND THAT OF THE |
| | OPEN VENT. |
| | |
| | 4) 2ND REQUEST, SINCE THE CHILDREN ARE GOING INTO THE |
| | REMAINDER OF THE HOUSE TO USE THE BATHROOM FACILITIES |
| | THEY WILL BE GOING PAST CLOSET DOORS, SHOW COMPLIANCE |
| | WITH: 2010FBC-B |
| | 436.2 CLOSET DOORS. |
| | EVERY CLOSET DOOR LATCH SHALL BE SUCH THAT CLIENTS CAN |
| | OPEN THE DOOR FROM INSIDE THE CLOSET. |
| | |
| | 5) RESPONSE TO SMOKE DETECTOR COMMENT ,ELECTRIC SMOKE |
| | DETECTORS ARE IN THE OFFICE (SLEEPING ROOM) |
| | PLEASE SHOW COMPLIANCE WITH ALL OF 436.10.5. |
| | 436.10.5 SMOKE DETECTION SYSTEMS. |
| | |
| | 436.10.5.1 |
| | SINGLE-STATION SMOKE ALARMS INSTALLED IN ACCORDANCE |
| | WITH THE HOUSEHOLD FIRE WARNING EQUIPMENT REQUIREMENTS |
| | OF CHAPTER 2 OF NFPA 72 SHALL BE INSTALLED WITHIN DAY |
| | CARE HOMES. |
| | |
| | EXCEPTION: SYSTEM SMOKE DETECTORS INSTALLED IN |
| | ACCORDANCE WITH NFPA 72 AND ARRANGED TO FUNCTION IN THE |
| | SAME MANNER SHALL BE PERMITTED. |
| | |
| | 436.10.5.2 |
| | WHERE THE DAY CARE HOME IS LOCATED WITHIN A BUILDING OF |
| | ANOTHER OCCUPANCY, ANY CORRIDORS SERVING THE DAY CARE |
| | HOME SHALL BE PROVIDED WITH A COMPLETE SMOKE DETECTION |
| | SYSTEM INSTALLED IN ACCORDANCE WITH NFPA 72. |
| | |
| | 436.10.5.3 |
| | SINGLE-STATION SMOKE ALARMS SHALL BE POWERED BY THE |
| | BUILDING ELECTRICAL SYSTEM. |
| | |
| | 436.10.5.4 |
| | SINGLE-STATION SMOKE ALARMS SHALL BE PROVIDED IN ALL |
| | ROOMS USED FOR SLEEPING. |
| | |
| | 436.10.5.5 |
| | WHERE TWO OR MORE SMOKE ALARMS ARE REQUIRED WITHIN A |
| | LIVING UNIT, SUITE OF ROOMS, OR SIMILAR AREA, THEY |
| | SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM |
| | SHALL CAUSE ALL SMOKE ALARMS WITHIN THE LIVING UNIT, |
| | SUITE OF ROOMS OR SIMILAR AREA TO SOUND. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |