| Date |
Text |
| 2014-04-11 10:51:25 | 3421 NORTH AUSTRALIAN AVENUE |
| | PERMIT #14030980 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | CHANGE FROM 5 CLIENTS TO 12 CLIENTS |
| | |
| | INDICATE THE AGE RANGE OF CLIENTS AND THE HOURS OF |
| | OPERATION AT THIS ADDRESS. |
| | |
| | INDICATE ALL ROOMS AND AREAS THAT WILL OCCUPY DAY-CARE |
| | CLIENTS AND WHICH ROOMS WILL BE USED FOR SLEEPING. |
| | |
| | SINGLE-STATION OR MULTIPLE-STATION SMOKE ALARMS OR |
| | SMOKE DETECTION SHALL BE PROVIDED IN ALL ROOMS USED FOR |
| | SLEEPING. |
| | |
| | PROVIDE A FURNITURE LAYOUT FOR ROOMS WITH DAY-CARE |
| | CLIENTS (TABLES, BEDS, CRIBS, ETC.) |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| | CLIENTS. |
| | |
| | AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN |
| | BUILDING PRIOR TO OCCUPANCY. EMERGENCY EGRESS DRILLS |
| | SHALL BE CONDUCTED MONTHLY. |
| | |
| | FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY |
| | BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A |
| | COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN |
| | A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL |
| | BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO |
| | ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED |
| | CLEAR OF OBSTRUCTIONS. |
| | |
| | ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS |
| | SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL |
| | AREA. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |