Plan Review Notes
Plan Review Notes For Permit 14030916
Permit Number 14030916
Review Stop M
Sequence Number 1
Notes
Date Text
2014-04-01 07:17:392010 FBC
  
 DENIED BY MECHANICAL
  
 1) SPECIFY THE SIZE OF ALL OF THE DUCTS SHOWN ON THE
 PLANS. CITY AMENDMENTS 107.3.5.3
  
 2) PROVIDE TWO SETS OF EQUIPMENT SIZING CALCULATIONS AS
 REQUIRED BY FBCR M1401.3.
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT
 MATCHES THE SIZING CALCULATIONS. CITY AMENDMENTS
 107.2.1
  
 4) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED
 RETURN AIR.
  
 5) SHOW THE LOCATION OF THE CONDENSING UNIT ON THE
 PLANS AND SHOW HOW IT WILL BE INSTALLED AND ANCHORED TO
 RESIST WIND LOADS. CITY AMENDMENTS 107.3.5.3 AND FBCR
 M1307.2.1 & M1401.4
  