| Plan Review Notes For Permit 14030916 |
| Permit Number |
14030916 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-01 07:17:39 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SPECIFY THE SIZE OF ALL OF THE DUCTS SHOWN ON THE | | | PLANS. CITY AMENDMENTS 107.3.5.3 | | | | | | 2) PROVIDE TWO SETS OF EQUIPMENT SIZING CALCULATIONS AS | | | REQUIRED BY FBCR M1401.3. | | | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT | | | MATCHES THE SIZING CALCULATIONS. CITY AMENDMENTS | | | 107.2.1 | | | | | | 4) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | | RETURN AIR. | | | | | | 5) SHOW THE LOCATION OF THE CONDENSING UNIT ON THE | | | PLANS AND SHOW HOW IT WILL BE INSTALLED AND ANCHORED TO | | | RESIST WIND LOADS. CITY AMENDMENTS 107.3.5.3 AND FBCR | | | M1307.2.1 & M1401.4 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|