| Plan Review Notes For Permit 14030856 |
| Permit Number |
14030856 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-16 12:32:03 | IT APPEARS AND ADDITIONAL STROBE DEVICE NEAR CHAIR 18 | | | AND CHAIR 19 IS NEEDED TO PROVIDE ADEQUATE VISUAL | | | NOTIFICATION. | | | | | | PER LOCAL REQUIREMENTS, DUCT DETECTORS SHALL ACTIVATE A | | | GENERAL ALARM CONDITION IN LIEU OF A SUPERVISORY | | | CONDITION. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WPB FIRE RESCUE | | | 561.804.4752 | | | [email protected] |
|