| 2014-04-01 06:15:11 | BUILDING PLAN REVIEW |
| | PERMIT: 14030855 |
| | ADD: 2101 OKEECHOBEE BLVD |
| | CONT: HEDRICK BROTHERS |
| | TEL: (561)689-8880 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE:MON-TUESDAY MARCH 31/ APRIL 1/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SOILS REPORT BY TIERRA SOURH FLORIDA ARE COPIES, |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS/ EFFECTIVE DATE |
| | 05/06/2009 |
| | |
| | 2) WITHIN THE FOUNDATION SET OF PLANS SHEET S-0.1 |
| | HEADING 31000 FOUNDATION. SEE THE FOLLOWING REPORTFOR |
| | COMPLETE GEOTECHNICAL RECOMMENDATIONS AND INSTALATION |
| | PREOCEDURES: |
| | REPORT # 7111-13-202 |
| | PREPARED BY TIERRA SOUTH FLORIDA, INC |
| | DATED AUGUST 16, 2013 |
| | THIS REPORT SHALL BE CONSIDERED PART OF THE CONTRACT |
| | DOCUMENTS FOUNDATION-DESIGN IS BASED ONA A SOIL BEARING |
| | PRESSURE OF 3000 PSF. |
| | |
| | IN THE REPORT # 7111-13-202 PREPARED BY TIERRA SOUTH |
| | FLORIDA PAGE 1 UNDER THE HEADING 1.0 EXECUTIVE SUMMARY |
| | WE RECOMMEND TEST PITS BE PREFORMED IN THE BUILDING |
| | AREAS TO ASSESS THE EXTENT OF ORGANICS (MUCKS). |
| | |
| | THERE WAS NO SUBMSSTION INDICATING COMPLIANCE WITH THE |
| | RECOMMEND TEST PITS BE PREFORMED IN THE BUILDING AREAS |
| | TO ASSESS THE EXTENT OF ORGANICS (MUCKS). 2010 FBC-B |
| | 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, |
| | STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR |
| | WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED |
| | IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| | BE CONDUCTED. |
| | |
| | 3) THE PLANS INDICATE THIS PROJECT BE TILT WALL |
| | REQUIRING A RESIDENT INSPECTOR. THREE (3) SETS OF ALL |
| | PLANS AND SUBMITTALS. 2010 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 EDITION 110.3.9 OTHER INSPECTIONS |
| | SERVICES. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO |
| | BE MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION |
| | 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF |
| | RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F ?C) IN EXCESS OF 3000 |
| | POUNDS PER SQUARE INCH |
| | 4. FOR PILE DRIVING |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT |
| | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION (TILT WALL) |
| | |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| | ARCHITECT, OR ENGINEER, OR A |
| | PERSON LICENSED UNDER CHAPTER 468, PART XII, FLORIDA |
| | STATUTES. SUCH INSPECTORS SHALL SUBMIT WEEKLY PROGRESS |
| | REPORTS INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| | OFFICIAL, AND INCLUDING A |
| | CODE COMPLIANCE OPINION OF THE RESIDENT INSPECTOR. AT |
| | THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT, |
| | SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF |
| | COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE |
| | WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN |
| | ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION |
| | SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A |
| | CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION |
| | IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT |
| | ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |