| 2014-04-09 14:35:55 | ELECTRICAL PROVOSO: THOUGH NOT INDICATED ON THE | | | APPROVED DRAWINGS, THE EXISTING POWER SUPPLY AND THE | | | ELECTRIC ROOM SHALL BE PROTECTED BY A SMOKE DETECTOR AS | | | REQUIRED BY FBC & NFPA 72. | | | ALL DOCUMENTATION AS REQUIRED BY NFPA 72 SECTION 4.5 | | | SHALL BE PROVIDED UPON COMPLETION AND AVAILABLE FOR | | | INSPECTION. | | | FOR FINAL INSPECTION, THIS SYSTEM SHALL UNDERGO A | | | REACCEPTANCE TEST AS REQUIRED BY NFPA 72 SECTION | | | 10.4.1.2; RECORDS OF THAT SHALL BE KEPT IN THE SYSTEM | | | LOG AS REQUIRED. | | | |
|