| Plan Review Notes For Permit 14030818 |
| Permit Number |
14030818 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-04-07 12:55:57 | 4/7/15 | | | PROJECT: 525 CLEMATIS | | | PERMIT#: 14030818 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 4TH ELECTRICAL PLAN REVIEW | | | ACTION: APPROVED WITH EXCEPTION. | | | | | | 1) ATOMIC TIMER IS NOT APPROVED FOR LIGHTING CONTROL AS | | | DEFINED IN THE FBC 505.2 REVISE PLANS AND INSTALLATION | | | FOR AN APPROVED LIGHTING CONTROL METHOD. FBC - E 505.2 | | | | | | 2) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE | | | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND | | | SPECIFIC PURPOSE OR USE. NEC 408.4. REVISE PANEL | | | SCHEDULE TO COMPLY. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | | | 2015-04-01 09:23:40 | NEW DRAWINGS SUBMITTED. JG. |
|