| 2014-11-27 09:28:37 | 1)TABLE 403.1 FOOTNOTE "G" OF 2010 FL. PLUMBING CODE |
| | REQUIRES A UNISEX BATHROOM IN ASSEMBLY OCCUPANCIES |
| | WHERE AN AGGREGATE OF SIX OR MORE MALE AND FEMALE WATER |
| | CLOSETS ARE REQUIRED IN ACCORDANCE WITH THE 2010 FPC |
| | SEC.403.5. SHOW THE REQUIRED UNISEX TOILET ROOM ON THE |
| | PLANS AND PROVIDE A SANITARY AND WATER RISER FOR |
| | REVIEW. 2ND REQUEST. THE UNISEX TOILET ROOM SHALL |
| | COMPLY WITH THE FL. ACCESSIBILITY CODE. |
| | 2) SUBMIT AN ENLARGED RESTROOM FLOOR PLAN FOR THE FIRST |
| | FLOOR. SHOW ALL REQUIRED FLOOR SPACE FOR THE |
| | HANDICAPPED FIXTURES. THE RESTROOMS SHALL FULLY COMPLY |
| | WITH THE 2010 FL. ACCESSIBILITY CODE.THE TOILET |
| | COMPARTMENTS SHALL COMPLY WITH FAC SEC.604.8.1.6.SINCE |
| | THIS IS A CHANGE OF OCCUPANCY. 2ND REQUEST. |
| | 3) SHT. P-2 - THE FIRST FLOOR SANITARY PLAN IS DRAWN |
| | VERY LIGHT AND IS DIFFICULT TO READ. SUBMIT A PLAN THAT |
| | IS CLEAR IN DETAIL AND LEGIBLE. WPB AMEND. TO 2001 FBC |
| | SEC. 107.2.1. 2ND REQUEST. |
| | 4) THE RESTROOMS ON THE 2ND FLOOR SHALL FULLY COMPLY |
| | WITH THE FL. ACCESSIBILITY CODE. THE TOILET |
| | COMPARTMENTS SHALL COMPLY WIT FAC SEC.604.8.1.6.SHOW |
| | ALL THE REQUIRED CLEAR FLOOR SPACE PER FAC SEC. 306 & |
| | 604.3.2ND REQUEST. |
| | 5) SHT. P-4 - THE 2ND FLOOR SANITARY ISOMETRIC FOR THE |
| | WOMEN'S RESTROOM #205 HAS A DRY VENT FOR THE P-1 |
| | FIXTURE. EVERY DRY VENT CONNECTING TO A HORIZONTAL |
| | DRAIN SHALL COMPLY WITH THE 2010 FPC SEC.905.3. 2ND |
| | REQUEST. |
| | 6) THE FLOOR DRAINS ON THE FIRST FLOOR SANITARY |
| | ISOMETRIC ARE NOT VENTED. PROVIDE THE PROPER SIZE VENTS |
| | PER THE FPC SEC.906.1, 901.2. 2ND REQUEST. |
| | 7) THE P-5 FIXTURE SHALL BE PROPERLY TRAPPED. FPC |
| | 1002.1. 2ND REQUEST. |
| | 8) THE SINGLE FLOOR DRAIN IN THE BAR AREA (#209) IS NOT |
| | VENTED.FPC SEC.906.1.2ND REQUEST. |
| | 9)THE NUMBER OF WATER CLOSETS BEING WET VENTED IN THE |
| | FIRST AND SECOND FLOOR RESTROOMS EXCEEDS THE NUMBER |
| | PERMITTED BY FPC SEC. 909. ALSO, URINALS ARE NOT |
| | PERMITTED ON THE HORIZONTAL WET VENTS. 2ND REQUEST. |
| | 10) SHT. P-3 - THE 2ND FLOOR DOMESTIC (WATER PLAN) IS |
| | DRAWN VERY LIGHT AND IS DIFFICULT TO READ. SUBMIT A |
| | PLAN THAT IS CLEAR IN DETAIL AND LEGIBLE. WPB AMEND. TO |
| | 2001 FBC SEC. 107.2.1. |
| | 11) THE RESPONSE NARRATIVE FROM ELLIS & GRITTER |
| | ADDRESSES COMMENTS FROM THE APRIL REVIEW NOT THE |
| | NOVEMBER REVIEW. |
| | |