| 2014-12-17 15:50:13 | 12/17/2014 |
| | PROJECT: 525 CLEMATIS |
| | PERMIT#: 14030818 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. |
| | |
| | 1) ATOMIC TIMER IS NOT APPROVED FOR LIGHTING CONTROL AS |
| | DEFINED IN THE FBC 505.2 REVISE PLANS AND INSTALLATION |
| | FOR AN APPROVED LIGHTING CONTROL METHOD |
| | |
| | 2) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE |
| | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| | SPECIFIC PURPOSE OR USE. NEC 408.4. REVISE PANEL |
| | SCHEDULE TO COMPLY. |
| | |
| | 3) PROVIDE A COMPREHENSIVE AS BUILT REVISION FOR |
| | ELECTRICAL LOAD SUMMARY CALCULATION BASED ON NEC |
| | ARTICLE 220, |
| | |
| | 4) REVISE THE ELECTRICAL SERVICE RISER DIAGRAM WITH |
| | SIZES OF ALL CONDUIT AND WIRE, |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |