| 2014-12-08 12:14:00 | BUILDING PLAN REVIEW |
| | PERMIT: 14030818 |
| | ADD: 526 CLEMATIS ST 1ST FLOOR & 2ND FLOOR- CHANGE OF |
| | OCCUPANY/INTERIOR & EXTERIOR |
| | CONT: JM PROPERTIES OF WEST PALM BEACH, INC |
| | TEL: (561)756-5744 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | BLDG TYPE III-B SPRINKLERED |
| | |
| | 3RD REVIEW |
| | DATE: MON. DEC. 08/ 2014 |
| | ACTION: BUILDING PROVISO |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | THE LAST RENOVATIONS TO THIS BUILDING UNDER PERMIT |
| | 03060274, FIRST FLOOR MERCANTILE AND THE 2ND FLOOR R2 |
| | APARTMENTS, THIS REVIEW WILL BE CONSIDERED A CHANGE IN |
| | OCCUPANCY AND CHAPTER 9 OF THE EXISITNG BUILDING CODE. |
| | 901.3 CHANGE OF OCCUPANCY CLASSIFICATION. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| | OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| | GROUP. |
| | |
| | |
| | CONTRACTOR IS PROCEEDING AT THEIR OWN RISK!!! 2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION, 105.13 PHASED PERMIT |
| | APPROVAL. AFTER SUBMITTAL OF THE APPROPRIATE |
| | CONSTRUCTION DOCUMENTS, THE BUILDING OFFICIAL IS |
| | AUTHORIZED TO ISSUE A PERMIT FOR THE CONSTRUCTION OF |
| | FOUNDATIONS OR ANY OTHER PART OF A BUILDING OR |
| | STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS FOR THE |
| | WHOLE BUILDING OR STRUCTURE HAVE BEEN SUBMITTED. THE |
| | HOLDER OF SUCH PERMIT FOR THE FOUNDATION OR OTHER PARTS |
| | OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE |
| | HOLDER?S OWN RISK WITH THE BUILDING OPERATION AND |
| | WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| | STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED |
| | TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS |
| | PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL |
| | OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST |
| | BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. |
| | |
| | 1) REVISION REQUIRED. AN ARCHITECTURAL SHEET IS |
| | REQUIRED SHOWING THE SCHEMATIC LAYOUT FOR THE FIRE |
| | SPRINKLERS, A FULL NFPA 13 SYSTEM WILL BE REQUIRED. |
| | A HOLD WILL BE PUT ON THE CERTIFICATE OF OCCUPANCY |
| | UNTIL THIS REVISION IS SUBMITTED AND APPROVED. SEPARATE |
| | FIRE SPRINKLER PLANS WILL ALSO NEED TO BE SUBMITTED BY |
| | THE ENGINEER OF RECORD AND REVIEWED BY THE DESIGNER OF |
| | RECORD WITH THIER SHOP DRAWING STAMP OF APPROVAL, |
| | APPROVED OR APPROVED WITH COMMENTS. |
| | |
| | 107.2.1.1 FIRE PROTECTION SYSTEM SHOP DRAWINGS. SHOP |
| | DRAWINGS FOR THE FIRE PROTECTION SYSTEM(S) SHALL BE |
| | SUBMITTED TO INDICATE CONFORMANCE WITH THIS CODE AND |
| | THE CONSTRUCTION DOCUMENTS AND SHALL BE APPROVED PRIOR |
| | TO THE START OF SYSTEM INSTALLATION. SHOP DRAWINGS |
| | SHALL CONTAIN ALL INFORMATION AS REQUIRED BY THE |
| | REFERENCED INSTALLATION STANDARDS IN CHAPTER 9. |
| | |
| | 3RD REQUEST. MON. DEC. 08/2014 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION,107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | (5) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | SCHEMATIC FIRE SPRINKLERS |
| | STANDPIPES |
| | PRE-ENGINEERED SYSTEMS |
| | |
| | THE COVERSHEET A0.0 INDICATES THIS BUILDING TO BE FIRE |
| | SPRINKLERED, BUT THERE IS NO MENTION OF A FIRE |
| | SPRINKLER PLAN IN THE INDEX OF DRAWINGS NOR ANYWHERE |
| | ELSE IN THE PLANS. TRAVEL DISTANCES ARE SHOWN FOR |
| | NON-SPRINKLERED BUILDING. |
| | 2010 EXST BLDG CODE 904.1 GENERAL. |
| | FIRE PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY |
| | WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE |
| | OF OCCUPANCY CLASSIFICATION. |
| | 912.2 FIRE PROTECTION SYSTEMS. |
| | FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTIONS 912.2.1 AND 912.2.2. |
| | |
| | EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. |
| | |
| | 2010 FBC-B F] 903.2.1.2 GROUP A-2. |
| | AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR |
| | GROUP A-2 OCCUPANCIES WHERE ONE OF THE FOLLOWING |
| | CONDITIONS EXISTS: |
| | 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2); |
| | 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE; |
| | |
| | EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| | APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| | THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| | FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED. |
| | |
| | BUILDING PROVISO: |
| | 10C) FRONT ENTRY REDESIGN: |
| | 10C)(1) MISSING PRODUCT APPROVALS 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS:(31)(A) EXTERIOR DOORS. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |