| 2014-09-30 13:48:11 | 14030818 |
| | 526 CLEMATIS ST. |
| | INTERIOR RENOVATION |
| | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. MANY OF THESE COMMENTS WERE PREVIOUSLY |
| | PROVIDED ( 4/3/14) ON THE FIRST REVIEW. |
| | |
| | |
| | VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A |
| | FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL |
| | CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. SHOW THE FAULT CURRENT RATING OF THE MAIN |
| | DISCONNECTS AND PANELBOARDS. NEC 110.9 |
| | |
| | PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.14; 220.40 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING |
| | MEANS. NEC 110.22, 110.16, 110.22 |
| | |
| | ON THE ELECTRIC PLAN SHOW ALL REQUIRED ACCESS AND SAFE |
| | WORKING CLEARANCES FOR THE ELECTRICAL SERVICE, MAIN |
| | DISCONNECTS AND PANEL BOARDS. NEC 110.26 |
| | |
| | ON THE PANEL SCHEDULE INCLUDE THE SHOW WINDOW LIGHTING |
| | AND A SIGN CIRCUIT. NEC 210.62, 408.4, 600.5 |
| | |
| | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS IN THE |
| | BAR MUST BE GFCI PROTECTED. NEC 210.8 |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING |
| | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 |
| | |
| | PROVIDE LIGHTING CONTROLS FOR ENERGY CONSERVATION SO |
| | THAT THE INTERIOR AND EXTERIOR LIGHTING CONTROLS |
| | PROVIDED FUNCTION IN ACCORDANCE WITH THE FLORIDA ENERGY |
| | CODE. EXTERIOR AUTOMATIC CONTROLS SHALL BE CAPABLE OF |
| | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS |
| | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. VERIFY THE |
| | LIGHTING AND SIGN TIME CLOCKS HAVE BATTERY BACKUP. FBC |
| | ENERGY CONSERVATION 505.2 |
| | |
| | ON THE ELECTRIC PLAN PROVIDE A LIGHTING SCHEDULE |
| | SHOWING FIXTURE SELECTION. INCLUDE EXIT LIGHTING WITH |
| | BATTERY BACKUP. FBC, ENERGY CONSERVATION 502.3.8; FBC |
| | 1011 |
| | |
| | ADD THE EXIT LIGHTING CIRCUIT TO THE LIGHTING PANEL. |
| | NEC 408.4 |
| | |
| | PROVIDE GFCI PROTECTED RECEPTACLES ON THE ROOF TO |
| | SERVICE THE MECHANICAL EQUIPMENT ON THE ROOF. NEC |
| | 210.8(B), 210.63 |
| | |
| | REVISE ELECTRICAL RISER PLAN TO SHOW PANEL ?EV?. SHOW |
| | FEEDER SIZE FOR PANEL ?B?. PROVIDE OVER CURRENT |
| | PROTECTION FOR PANEL ?A?. SHOW LOCATION OF PANEL ?A?. |
| | NEC 215.5 |
| | |
| | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE |
| | ELEVATOR, ALARM SYSTEMS, SECURITY AND DATA SYSTEMS. |
| | |
| | ROBERT LECKY, CBO |
| | ELECTRICAL PLANS REVIEW |