| Date |
Text |
| 2014-10-08 08:15:40 | BUILDING PLAN REVIEW |
| | PERMIT: 14030818 |
| | ADD: 526 CLEMATIS ST 1ST FLOOR & 2ND FLOOR- CHANGE OF |
| | OCCUPANY/INTERIOR & EXTERIOR |
| | CONT: JM PROPERTIES OF WEST PALM BEACH, INC |
| | TEL: (561)756-5744 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | BLDG TYPE III-B SPRINKLERED |
| | |
| | 2ND REVIEW |
| | DATE: WEDNESDAY 08/ 2014 |
| | ACTION: DENIED |
| | |
| | THE LAST RENOVATIONS TO THIS BUILDING UNDER PERMIT |
| | 03060274, FIRST FLOOR MERCANTILE AND THE 2ND FLOOR R2 |
| | APARTMENTS, THIS REVIEW WILL BE CONSIDERED A CHANGE IN |
| | OCCUPANCY AND CHAPTER 9 OF THE EXISITNG BUILDING CODE. |
| | 901.3 CHANGE OF OCCUPANCY CLASSIFICATION. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| | OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| | GROUP. |
| | |
| | 1) THE COVERSHEET A0.0 INDICATES THE OCCUPANCY AS A A2 |
| | NIGHTCLUB SINCE THERE IS NO KITCHEN SHOWN ON THE PLANS. |
| | SHEET A1.2 LIST OCCUPANT LOADS FOR EACH FLOOR EXAMPLE |
| | THE 2ND FLOOR LIST CUSTOMER AREA 992 SQ. FT./ 198 |
| | OCCUPANTS + 32 +16+ 8 +6 +10. PLEASE PROVIDE WHERE THE |
| | ADDITIONAL |
| | OCCUPANT LOADS ARE TAKEN FROM, INDICATE THE AREA AND |
| | LOADING FACTOR. |
| | 2010 FBC-B 1004.2 INCREASED OCCUPANT LOAD. |
| | THE OCCUPANT LOAD PERMITTED IN ANY BUILDING, OR PORTION |
| | THEREOF, IS PERMITTED TO BE INCREASED FROM THAT NUMBER |
| | ESTABLISHED FOR THE OCCUPANCIES IN TABLE 1004.1.1, |
| | PROVIDED THAT ALL OTHER REQUIREMENTS OF THE CODE ARE |
| | ALSO MET BASED ON SUCH MODIFIED NUMBER AND THE OCCUPANT |
| | LOAD DOES NOT EXCEED ONE OCCUPANT PER 7 SQUARE FEET |
| | (0.65 M2) OF OCCUPIABLE FLOOR SPACE. WHERE REQUIRED BY |
| | THE BUILDING OFFICIAL, AN APPROVED AISLE, SEATING OR |
| | FIXED EQUIPMENT DIAGRAM SUBSTANTIATING ANY INCREASE IN |
| | OCCUPANT LOAD SHALL BE SUBMITTED. WHERE REQUIRED BY THE |
| | BUILDING OFFICIAL, SUCH DIAGRAM SHALL BE POSTED. |
| | |
| | 2) 2ND REQUEST. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION,107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | (5) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | SCHEMATIC FIRE SPRINKLERS |
| | STANDPIPES |
| | PRE-ENGINEERED SYSTEMS |
| | |
| | THE COVERSHEET A0.0 INDICATES THIS BUILDING TO BE FIRE |
| | SPRINKLERED, BUT THERE IS NO MENTION OF A FIRE |
| | SPRINKLER PLAN IN THE INDEX OF DRAWINGS NOR ANYWHERE |
| | ELSE IN THE PLANS. TRAVEL DISTANCES ARE SHOWN FOR |
| | NON-SPRINKLERED BUILDING. |
| | 2010 EXST BLDG CODE 904.1 GENERAL. |
| | FIRE PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY |
| | WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE |
| | OF OCCUPANCY CLASSIFICATION. |
| | 912.2 FIRE PROTECTION SYSTEMS. |
| | FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTIONS 912.2.1 AND 912.2.2. |
| | |
| | EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. |
| | |
| | 2010 FBC-B F] 903.2.1.2 GROUP A-2. |
| | AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR |
| | GROUP A-2 OCCUPANCIES WHERE ONE OF THE FOLLOWING |
| | CONDITIONS EXISTS: |
| | 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2); |
| | 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE; |
| | |
| | EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| | APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| | THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| | FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED. |
| | |
| | 3) COMPLIED, NEW INSWING FOLDING DOOR SYSTEM SHOWN ON |
| | PLANS. |
| | |
| | |
| | 4) SEMI-COMPLIED. THE (2) EXISTING SWING DOORS NEED TO |
| | SHOW THEY DO NOT SWING OUT OVER THE PROPERTY LINE AND |
| | IN COMPLIANCE WITH 2010 FBC-B |
| | 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN |
| | HEIGHT. PROVIDE A SITE PLAN AND OR SURVEY SHOWING CODE |
| | COMPLIANCE. |
| | |
| | 5) 2ND REQUEST. THE PLANS DO NOT HAVE ANY DETAILS AS |
| | FAR AS THE SILL FOR THE FOLDING DOOR SYSTEM, PLEASE |
| | PROVIDE COMPLIANCE WITH 2010 FL ACCESS CODE 404.2.5 |
| | THRESHOLDS. |
| | THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH |
| | (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN |
| | LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303. |
| | |
| | 6) SEMI-COMPLIED. SHEET A1.1 THE FRONT STAIR IS AN |
| | UNENCLOSED EXIT STAIRWAY AND TAKING THE EXEMPTION# 3 IN |
| | SECTION 1016.1. PLEASE PROVIDE THE WIDTH BOTH STAIRS |
| | AND THE ALLOWABLE OCCUPANT LOADS EACH STAIR WILL |
| | ACCEPT. 2010 FBC-B 1005.1. |
| | |
| | 7) SHEET A1.1 THE ELEVATOR MACHINE ROOM 2010 FBC-B |
| | 3006.4. PLEASE NOTE THE CEILING OF THIS ROOM WILL NEED |
| | TO BE FIRE RATED AS WELL IT WILL ABUT THE FRAMING |
| | MEMBERS OF THE STAIRWELL. 2010 FBC-B 1022.1 & 707 |
| | HORIZONTAL ASSEMBLIES. DOOR RATING 3/4 HR FIRE BARRIER |
| | TABLE 715.4. |
| | |
| | 8-9) COMPLIED. |
| | |
| | 10) STRUCTURAL SHEET S-1: |
| | |
| | 10A) STRUCTURAL SHEET ELEVATOR DETAIL IS MISSING THE |
| | FOLLOWING : |
| | 10A)(1) TB- HEIGTH NOT PROVIDED. NOTE TO MATCH |
| | EXISTING, NOTE THIS IS A (2) STORY SHAFT AND THERE IS |
| | NO DETAIL AS TO HOW THE TOP OF THE SHAFT FINISHES, |
| | BELOW THE ROOF OR ABOVE THE ROOF. 2010 FBC-B 708.12 |
| | 10A)(2) COMPLIED. |
| | 10A)(3) ELEVATOR DOES NOT SHOW A PIT OR RECESS FOR THE |
| | FLOOR OF THE ELEVATOR CAB TO BE LEVEL WITH THE FLOOR. |
| | 10)(4) THE ELEVATOR SHAFT DOES NOT CONTINUE THROUGH THE |
| | SECOND FLOOR. |
| | 10)(5) SHAFT ENCLOSURE, 2010 FBC-B 708.12 ENCLOSURE AT |
| | THE TOP. A SHAFT ENCLOSURE THAT DOES NOT EXTEND TO THE |
| | UNDERSIDE OF THE ROOF SHEATHING, DECK OR SLAB OF THE |
| | BUILDING SHALL BE ENCLOSED AT THE TOP WITH CONSTRUCTION |
| | OF THE SAME FIRE-RESISTANCE RATING AS THE TOPMOST FLOOR |
| | PENETRATED BY THE SHAFT, BUT NOT LESS THAN THE |
| | FIRE-RESISTANCE RATING REQUIRED FOR THE SHAFT |
| | ENCLOSURE. |
| | |
| | |
| | 10B)COMPLIED. |
| | |
| | 10C) FRONT ENTRY REDESIGN: |
| | 10C)(1) MISSING PRODUCT APPROVALS 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS:(31)(A) EXTERIOR DOORS. |
| | |
| | 10C)(2) MISSING DIMENSIONS, NO INFORMATION FOR VERTICAL |
| | NOR HORIZONTAL STEEL FRAMING MEMBERS, PRODUCT APPROVALS |
| | WILL NEED TO BE DECIDED TO BE ABLE TO PRODUCE THE |
| | SIZING OF THE ROUGH OPENING. 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 EDITION 107.2.1.3 ADDITIONAL DATA. |
| | THE BUILDING OFFICIAL MAY REQUIRE DETAILS, |
| | COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA NECESSARY |
| | TO DESCRIBE THE CONSTRUCTION OR INSTALLATION AND THE |
| | BASIS OF CALCULATIONS. ALL DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA REQUIRED BY THE BUILDING OFFICIAL TO |
| | BE PREPARED BY AN ARCHITECT OR ENGINEER SHALL BE |
| | AFFIXED WITH THEIR OFFICIAL SEAL, SIGNATURE AND DATE AS |
| | STATE LAW REQUIRES. |
| | SHEET S-1 INDICATES A DETAIL FOR THE FRONT ENTRY SHEET |
| | S-2 DETAIL # 7. THIS DETAIL INDICATES THE INSTALATION |
| | OF A W 16X31 BEAM TO AC1540 C CHANNEL. |
| | IN THIS SAME DETAIL AT THE BOTTOM OF THE DETAIL HERE |
| | APPEARS TO BE A BOX BEAM, THERE IS NO INFORMATION ON |
| | THE SIZE OF THIS BEAM OR HOW IT IS TO INSTALLED, IT |
| | APPEARS THIS THIS THE STRUCTURAL MEMBER (HEADER) FOR |
| | THE FOLDING DOOR SYSTEM. |
| | |
| | 10D) NEW COMMENT: THE NEW FRONT ENTRY CONFIGURATION NOW |
| | CONSIST OF A SINGLE SWING DOOR AND A FOLDING DOOR |
| | SYSTEM THAT HAS INCORPARATED A SWING DOOR AS PART OF |
| | THE FOLDING DOOR SYSTEM. PLEASE NOTE THAT BOTH OF THE |
| | FRONT SWING DOORS WILL BE REQUIRED AS PART OF THE |
| | EGRESS DOORS SINCE A 3'-0" DOOR WILL ALLOW 170 |
| | OCCUPANTS. PLEASE PROVIDE COMPLIANCE WITH 1008.1.10 |
| | PANIC AND FIRE EXIT HARDWARE, HOW WILL THIS REQUIREMENT |
| | WORK AS PART OF THE FOLDING DOOR SYSTEM? |
| | |
| | 11) COMPLIED. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |