| Date |
Text |
| 2014-04-16 08:44:54 | PLUMBING PLAN REVIEW |
| | PERMIT: 14030818 |
| | ADD: 526 CLEMATIS ST 1ST FLOOR CHANGE OF OCCUPANY/ |
| | EXTERIOR ALTERATIONS |
| | CONT: JM PROPERTIES OF WEST PALM BEACH, INC |
| | TEL: (561)756-5744 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | BLDG TYPE III-B SPRINKLERED |
| | |
| | 1ST REVIEW |
| | DATE: WED. APRIL 16/ 2014 |
| | ACTION: DENIED |
| | |
| | THE LAST RENOVATIONS TO THIS BUILDING UNDER PERMIT |
| | 03060274, FIRST FLOOR MERCANTILE AND THE 2ND FLOOR R2 |
| | APARTMENTS, THIS REVIEW WILL BE CONSIDERED A CHANGE IN |
| | OCCUPANCY AND CHAPTER 9 OF THE EXISITNG BUILDING CODE. |
| | 901.3 CHANGE OF OCCUPANCY CLASSIFICATION. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| | OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| | GROUP. |
| | |
| | 1) THE COVERSHEET A0.0 INDICATES THE 1ST FLOOR |
| | OCCUPANCY CLASSIFICATION AS A A-3, THE PLANS APPEAR TO |
| | BE A NIGHTCLUB OR BAR / TAVERN WHICH IS A A2 OCCUPANCY, |
| | SEE 2010 FBC-B 303.1. |
| | |
| | 2) NEITHER THE COVERSHEET NOR ANY OF THE PLUMBING |
| | SHEETS PROVIDE THE REQUIRED MINIMUM FIXTURE COUNT PER |
| | 2010 FBC-P TABLE 403.1. |
| | |
| | 3) THE PLANS DO NOTSTATE IF THIS TENANCY IS TO BE A |
| | RESTARAUNT OR A NIGHTCLUB. IF TO BE CONSIDERED A |
| | RESTARAUNT NO KITCHEN APPLIANCES HAVE BEEN SHOWN |
| | ALTHOUGH A 3 COMPARTMENT SINK IS SHOWN, PLEASE PROVIDE |
| | WHAT YPES OF FOOD WILL BE PREPARED. IF A RESTARAUNT |
| | THEN A SEPARATE PERMIT FOR A GREASE INTERCEPTOR WOULD |
| | BE REQUIRED. 2010 FBC-P 1003.3.1 GREASE INTERCEPTORS |
| | AND AUTOMATIC GREASE REMOVAL DEVICES REQUIRED. THE |
| | STORAGE ROOM APPEARS TO BE SET UP FOR A FUTURE KITCHEN |
| | WITH HOT AND COLD DOMESTIC WATER AND FLOOR DRAINS? |
| | |
| | 4) SHEET P3 SANITARY & DOMESTIC ISOMETRIC |
| | |
| | 4A) FLOOR DRAINS IN RESTROOM & STORAGE ROOM ARE MISSING |
| | TRAP PRIMERS. 2010 FBC-P 1002.4 TRAP SEALS. EACH |
| | FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS THAN |
| | 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 MM), |
| | OR DEEPER FOR SPECIAL DESIGNS RELATING TO ACCESSIBLE |
| | FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO LOSS BY |
| | EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE |
| | INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE |
| | TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A |
| | TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR |
| | ASSE 1044. |
| | |
| | 4B) FLOOR DRAINS AND TRAP PRIMER SEALS AND VENTING ARE |
| | MISSING ON THE SANITARY ISOMETRIC FOR THE STORAGE |
| | SUPPLY ROOM. 2010 FBC-P 905.3, & 1002.4. |
| | |
| | 4C) THE URINAL IN THE MENS RESTROOM DOES NOT SHOW ANY |
| | VENT, NOTE WET VENT SYSTEMS ARE ONLY FOR RESIDENTIAL 1 |
| | & 2 FAMILY USAGE. WOULD REQUIRE A INDIVIDUAL VENT. |
| | 2010 FBC-P 908.1, 909.1 AND BOAF INFORMAL |
| | INTERPRETATION REPORT # 6090, THESE INTERPRETATIONS ARE |
| | THE RESULT OF INPUT PROVIDED BY THE BOAF CODE |
| | DEVELOPMENT COMMITTEE, THE FLORIDA DEPARTMENT OF |
| | BUSINESS & PROFESSIONAL REGULATION (DBPR), THE |
| | INTERNATIONAL CODE COUNCIL (ICC) AND |
| | SUBJECT-MATTER-EXPERTS IN THE CONSTRUCTION |
| | INDUSTRY/PROFESSIONS. |
| | |
| | 4D) IN THE MENS RESTROOM THE LAV, URINAL NOR FLOOR |
| | DRAIN PROVIDE THE TRAP AND PIPE SIZES, 2010 FBC-P TABLE |
| | 709.1. |
| | |
| | 4E) IN THE FRONT BAR AREA WHERE THE 3 COMPARTMENT SINK, |
| | HAND SINK AND FLOOR SINK ARE SHOWN ON THE SANITARY |
| | ISOMETRIC, NONE OF THE BRANCH LINES AND TRAPS ARE |
| | SIZED, 2010 FBC-P TABLE 709.1. |
| | |
| | 4F) THE SANITARY ISOMETRIC DOES NOT PROVIDE WHAT SIZE |
| | ANY OF THE VENTS ARE AND IF REVENTED AND WHICH VENT IS |
| | GOING THROUGH TO THE ROOF? 2010 FBC-B 903.1.2. |
| | |
| | 4G) SHEET P2 SHOWS HOT AND COLD WATER BEING BROUGHT |
| | OVER INTO THE STORAGE ROOM BUT THEY ARE NOT SHOWWN ON |
| | THE DOMESTIC WATER ISOMETRIC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN |
| | APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. |
| | |
| | 5) SHEET P4: |
| | |
| | 5A) PIPE HANGER DETAILS SHOW I BEAM OR BAR JOIST HANGER |
| | AND ANCHORS FOR CONCRETE DECKS THE FLOOR SYSTEM IS WOOD |
| | TRUSS SYSTEM PLEASE SUPPLY THE APPROPRIATE DETAILS FOR |
| | THE INSTALATION. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | DISCREPANCY IN DETAILS, CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. |
| | 2010 FBC-P ; |
| | 308.3 MATERIALS. |
| | HANGERS, ANCHORS AND SUPPORTS SHALL SUPPORT THE PIPING |
| | AND THE CONTENTS OF THE PIPING. HANGERS AND STRAPPING |
| | MATERIAL SHALL BE OF APPROVED MATERIAL THAT WILL NOT |
| | PROMOTE GALVANIC ACTION. |
| | |
| | 308.4 STRUCTURAL ATTACHMENT. |
| | HANGERS AND ANCHORS SHALL BE ATTACHED TO THE BUILDING |
| | CONSTRUCTION IN AN APPROVED MANNER. |
| | |
| | 308.5 INTERVAL OF SUPPORT. |
| | PIPE SHALL BE SUPPORTED IN ACCORDANCE WITH TABLE 308.5. |
| | |
| | 5B) WATER HEATER RACK MOUNTING DETAIL, PLEASE PROVIDE |
| | INFORMATION ON THE RACK, RACK CARRYING CAPACITY AND |
| | TYPE OF ANCHORS TO BE USED AND TYPE OF MATERIAL THE |
| | ANCHORS WILL FASTENING INTO. 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 EDITION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. . |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |