| Date |
Text |
| 2014-04-02 13:44:06 | THE PERMIT PLAN WAS REVIEWED AND APPROVED WITH THE |
| | FOLLOWING COMMENTS BY PETER LEDUC, FIRE MARSHAL, BUREAU |
| | OF FIRE PREVENTION, WEST PALM BEACH FIRE RESCUE. |
| | |
| | 1. A FIRE SPRINKLER AND FIRE ALARM SYSTEM IS REQUIRED |
| | FOR THIS PROJECT. |
| | |
| | 2. ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO |
| | BE COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR |
| | AND SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, |
| | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY |
| | THE FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE |
| | SYSTEM. |
| | |
| | 3. ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A |
| | CERTIFIED FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA |
| | 72. A SEPARATE SHOP DRAWING IS REQUIRED TO BE |
| | SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION |
| | BUREAU PRIOR TO ANY WORK ON THE SYSTEM. |
| | |
| | 4. CURRENT LIFE SAFETY SYSTEMS, SPRINKLER AND/OR FIRE |
| | ALARM, SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION |
| | PERIOD. |
| | |
| | 5. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | 6. NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR |
| | ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR |
| | MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE |
| | PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY |
| | DOOR. |
| | |
| | 7. TWO (2) ADDITIONAL EXIT SIGNS ARE REQUIRED AS |
| | INDICATED DUE TO THE PROPOSED EXIT SIGNS BEING NOT |
| | VISIBLE FROM THE OCCUPIED AREAS THEY SERVE. |
| | |
| | 8. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS |
| | BUILDING. |
| | |
| | |