| 2014-04-03 14:23:19 | 14030818 |
| | 526 CLEMATIS ST. |
| | INTERIOR RENOVATION |
| | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | SHOW THE LOCATION OF ALL ELECTRICAL SERVICES WITH MAIN |
| | DISCONNECTS WHICH ARE SERVING THIS LOCATION. INCLUDE AN |
| | ELECTRICAL DEMOLITION PLAN FOR THE ANY EXISTING SERVICE |
| | OR INTERIOR ELECTRIC BEING RENOVATED. NEC 230.2, |
| | 230.71, 230.72 |
| | |
| | SHOW THE FEEDERS AND LOCATION FOR ALL MECHANICAL |
| | EQUIPMENT CIRCUITS AND DISCONNECTS. NEC 215.5 |
| | |
| | VERIFY THE EXISTING OCCUPANCY AND PANEL SCHEDULE |
| | INCLUDE THE SHOW WINDOW LIGHTING AND A SIGN CIRCUIT. |
| | NEC 210.62; 600.5 |
| | |
| | VERIFY THE ELECTRICAL SERVICE MAINS SERVING THIS |
| | BUILDING ARE SIX OR LESS AND GROUPED IN ONE LOCATION. |
| | NEC 230.2, 230.71, 230.72 |
| | |
| | SHOW ALL METERS, GROUNDING, MAIN DISCONNECTS, FEEDERS |
| | AND PANEL BOARDS FOR THE BUILDING SERVICE INCLUDING ALL |
| | OTHER EXISTING OCCUPANCIES REQUIRING ELECTRICAL |
| | SERVICE. |
| | NEC 215.5, 230.2, 230.71, 230.72 |
| | |
| | VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A |
| | FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL |
| | CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | VERIFY THE ELECTRICAL SERVICE LOAD IS NOT LESS THAN THE |
| | SUM OF ALL LOADS AS REQUIRED. NEC 215.5; 220.40 |
| | |
| | PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.14; 220.40 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING |
| | MEANS. NEC 110.22, 110.16, 110.22 |
| | |
| | ON THE ELECTRIC PLAN VERIFY AND SHOW ALL REQUIRED |
| | ACCESS AND SAFE WORKING CLEARANCES FOR THE ELECTRICAL |
| | SERVICE, MAIN DISCONNECT, ELEVATOR CONTROLLERS, |
| | ELEVATOR DISCONNECTS AND ALL PANELBOARDS. INCLUDE THE |
| | SECOND FLOOR. NEC 110.26; 620.5 |
| | |
| | INCLUDE THE REQUIRED ELEVATOR BRANCH CIRCUITS ON THE |
| | PANEL SCHEDULE AND IN THE LOAD CALCULATION. NEC 110.22; |
| | 408.4; 620.23, 620.24 |
| | |
| | REVISE THE ELECTRIC PANEL DIRECTORY SO THAT ALL |
| | CIRCUITS ARE IDENTIFIED AS TO THEIR SPECIFIC PURPOSE OR |
| | USE. INCLUDE ALL CIRCUITS FEEDING THE SECOND FLOOR. NEC |
| | 408.4 |
| | |
| | ADD THE EXIT LIGHTING CIRCUIT TO THE LIGHTING PANEL. |
| | NEC 408.4 |
| | |
| | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS IN THE |
| | BAR MUST BE GFCI PROTECTED. NEC 210.8 |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING |
| | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 |
| | |
| | VERIFY THE REQUIRED GFCI PROTECTED RECEPTACLE IS |
| | AVAILABLE TO SERVICE THE MECHANICAL EQUIPMENT. NEC |
| | 210.8(B) |
| | |
| | ON THE ELECTRIC PLAN PROVIDE A LIGHTING SCHEDULE |
| | SHOWING FIXTURE SELECTION INCLUDING EXIT LIGHTING WITH |
| | BATTERY BACK UP. FBC, ENERGY CONSERVATION 502.3.8; FBC |
| | 1011 |
| | |
| | INDICATE THE LOCATION OF THE ELEVATOR PANELBOARD. NEC |
| | 215.5 |
| | |
| | SHOW REQUIRED RECEPTACLES IN ELEVATOR EQUIPMENT ROOMS |
| | AND PITS WITH GFCI PROTECTION. NEC 620.23, 620.85 |
| | |
| | A SEPARATE BRANCH CIRCUIT SHALL SUPPLY ELEVATOR CAR |
| | LIGHTS. NEC 620.22 |
| | |
| | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE |
| | ELEVATOR, ALARM SYSTEMS, SECURITY AND DATA SYSTEMS. |
| | |
| | ROBERT LECKY, CBO |
| | ELECTRICAL PLANS REVIEW |
| | 561-373-3701 |
| | |
| | |