| Date |
Text |
| 2014-04-15 18:59:58 | BUILDING PLAN REVIEW |
| | PERMIT: 14030818 |
| | ADD: 526 CLEMATIS ST 1ST FLOOR CHANGE OF OCCUPANY/ |
| | EXTERIOR ALTERATIONS |
| | CONT: JM PROPERTIES OF WEST PALM BEACH, INC |
| | TEL: (561)756-5744 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | BLDG TYPE III-B SPRINKLERED |
| | |
| | 1ST REVIEW |
| | DATE: TUESDAY APRIL 16/ 2014 |
| | ACTION: DENIED |
| | |
| | THE LAST RENOVATIONS TO THIS BUILDING UNDER PERMIT |
| | 03060274, FIRST FLOOR MERCANTILE AND THE 2ND FLOOR R2 |
| | APARTMENTS, THIS REVIEW WILL BE CONSIDERED A CHANGE IN |
| | OCCUPANCY AND CHAPTER 9 OF THE EXISITNG BUILDING CODE. |
| | 901.3 CHANGE OF OCCUPANCY CLASSIFICATION. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| | OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| | GROUP. |
| | |
| | 1) THE COVERSHEET A0.0 INDICATES THE 1ST FLOOR |
| | OCCUPANCY CLASSIFICATION AS A A-3, THE PLANS APPEAR TO |
| | BE A NIGHTCLUB OR BAR / TAVERN WHICH IS A A2 OCCUPANCY, |
| | SEE 2010 FBC-B 303.1. |
| | |
| | 2) THE COVERSHEET A0.0 INDICATES THIS BUILDING TO BE |
| | FIRE SPRINKLERED, BUT THERE IS NO MENTION OF A FIRE |
| | SPRINKLER PLAN IN THE INDEX OF DRAWINGS NOR ANYWHERE |
| | ELSE IN THE PLANS. TRAVEL DISTANCES ARE SHOWN FOR |
| | NON-SPRINKLERED BUILDING. |
| | 2010 EXST BLDG CODE 904.1 GENERAL. |
| | FIRE PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY |
| | WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE |
| | OF OCCUPANCY CLASSIFICATION. |
| | 912.2 FIRE PROTECTION SYSTEMS. |
| | FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTIONS 912.2.1 AND 912.2.2. |
| | |
| | EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. |
| | |
| | 2010 FBC-B F] 903.2.1.2 GROUP A-2. |
| | AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR |
| | GROUP A-2 OCCUPANCIES WHERE ONE OF THE FOLLOWING |
| | CONDITIONS EXISTS: |
| | 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2); |
| | 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE; |
| | |
| | EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| | APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| | THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| | FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED. |
| | |
| | 3) SHEET A1.1 SHOWS NEW OUT SWING ENTRY DOORS PLEASE |
| | PROVIDE A SURVEY WITH THE DISTANCE FROM THE BUILDING TO |
| | THE PROPERTY LINE AT THE CLEMATIS OR FRONT OF THE |
| | BUILDING. 2010 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE |
| | AND BELOW 8 FEET IN HEIGHT. |
| | ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE |
| | AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE |
| | PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1 |
| | THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR |
| | PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | |
| | 4) SHEET A1.1 FRONT ENTRY AREA THERE IS A DISCREPANCY |
| | IN THE PLANS. THE 1ST FLOOR PLAN AND LIFE SAFETY PLAN |
| | SHOW TWO SWING ENTRY DOORS AND THE EXTERIOR FOLDING |
| | DOOR SYSTEM FOLDING OVER AND STCKING ALL THE WAY TO THE |
| | EAST OF THE OPENING, WHERE AS THE STRUCTURAL SHEET S1 |
| | SHOWS THE DOORS SPLITTING IN THE CENTER AND FOLDING |
| | EACH WAY. THE FOLDING DOOR SYSTEM THAT SPLITS IN THE |
| | MIDDLE WILL NOT ALLOW AN ACCESSIBLE ENRY AT THE SWING |
| | DOOR SINCE THERE WILL NOT BE 18 INCHES CLEAR AT THE |
| | LATCH SIDE OF THE DOOR 2010 FL ACCESS CODE 404.2.4.1 & |
| | FIGURE 404.2.4.1(A). |
| | |
| | 5) THE PLANS DO NOT HAVE ANY DETAILS AS FAR AS THE SILL |
| | FOR TTHE FOLDING DOOR SYSTEM, PLEASE PROVIDE COMPLIANCE |
| | WITH 2010 FL ACCESS CODE 404.2.5 THRESHOLDS. |
| | THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH |
| | (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN |
| | LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303. |
| | |
| | 6) SHEET A1.1 THE FRONT EXIT ENCLOSURE BOTH 1ST FLOOR & |
| | 2ND FLOOR LANDINGS SHOW THE ELEVATOR LOCATED IN THE |
| | EXIT ENCLOSURE. PLEASE REVIEW 2010 FBC-B 1022.3 & |
| | 1022.4. |
| | 2010 FBC-B 1022.3 |
| | EXIT ENCLOSURE OPENING PROTECTIVES SHALL BE IN |
| | ACCORDANCE WITH THE REQUIREMENTS OF SECTION 715. |
| | |
| | OPENINGS IN EXIT ENCLOSURES OTHER THAN UNPROTECTED |
| | EXTERIOR OPENINGS SHALL BE LIMITED TO THOSE NECESSARY |
| | FOR EXIT ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED |
| | SPACES AND FOR EGRESS FROM THE ENCLOSURE. |
| | |
| | ELEVATORS SHALL NOT OPEN INTO AN EXIT ENCLOSURE. |
| | |
| | 2010 FBC-B 1022.4 PENETRATIONS. |
| | PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT |
| | ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, |
| | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| | COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| | THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT |
| | EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| | PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| | SECTION 713. |
| | THERE SHALL BE NO PENETRATIONS OR COMMUNICATION |
| | OPENINGS, WHETHER PROTECTED OR NOT, BETWEEN ADJACENT |
| | EXIT ENCLOSURES. |
| | |
| | 6A)(1) 2010 FBC-B 707.3.2 EXIT ENCLOSURES. THE |
| | FIRE-RESISTANCE RATING OF THE FIRE BARRIER SEPARATING |
| | BUILDING AREAS FROM AN EXIT SHALL COMPLY WITH SECTION |
| | 1022.1. |
| | |
| | 6A)(2) 2010 FBC-B 708.5 CONTINUITY. SHAFT ENCLOSURES |
| | SHALL BE CONSTRUCTED AS FIRE BARRIERS IN ACCORDANCE |
| | WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| | IN ACCORDANCE WITH SECTION 712, OR BOTH, AND SHALL HAVE |
| | CONTINUITY IN ACCORDANCE WITH SECTION 707.5 FOR FIRE |
| | BARRIERS OR SECTION 712.4 FOR HORIZONTAL ASSEMBLIES AS |
| | APPLICABLE. |
| | |
| | 6A)(3) 2010 FBC-B 707.5 CONTINUITY. FIRE BARRIERS SHALL |
| | EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR/CEILING |
| | ASSEMBLY BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF |
| | SHEATHING, SLAB OR DECK ABOVE AND SHALL BE SECURELY |
| | ATTACHED THERETO. SUCH FIRE BARRIERS SHALL BE |
| | CONTINUOUS THROUGH CONCEALED SPACES, SUCH AS THE SPACE |
| | ABOVE A SUSPENDED CEILING. SHEET A3.1 DETAIL A1 SHOWS A |
| | DETAIL FOR A 1 HR FIRE RATED WALL, BUT THE DETAIL DOES |
| | NOT INDICATE HOW IT WILL DEAL WITH A WOOD FLOOR TRUSS |
| | SYSTEM, OR HOW THE FIRE RATING MAY OCCUR AROUND |
| | HEADERS, AND WOOD BUILT UP FLOOR TRUSS GIRDERS. |
| | |
| | 7) SHEET A1.1 LIFE SAFETY PLAN IS MISSING THE RATING OF |
| | WALLS AND DOORS: |
| | 7A) THE FRONT AND REAR STAAIRWELLS DO NOT INDICATTE A 1 |
| | HOUR FIRE RATED WALL ALL THE WAY AROUND THE ENCLOSURE, |
| | 2010 FBC-B 1022.1 AND THE REQUIRED FIRE RATED DOORS PER |
| | 2010 FBC-B 715 & TABLE 715.4 1 HOUR RATED DOORS . |
| | |
| | 7B) THE ELEVATOR MACHINE ROOM 2010 FBC-B 3006.4. PLEASE |
| | NOTTE THE CEILING OF THIS ROOM WILL NEED TO BE FIRE |
| | RATED AS WELL IT WILL ABUT THE FRAMING MEMBERS OF THE |
| | STAIRWELL. 2010 FBC-B 1022.1 & 707 HORIZONTAL |
| | ASSEMBLIES. DOOR RATING 3/4 HR FIRE BARRIER TABLE |
| | 715.4. |
| | |
| | 8) UNDER THE 03060274 PERMIT THE STAIR ENCLOSURE AND |
| | ELEVATOR WERE A DIFFERENT CONFIGURATION, THE PLANS DO |
| | NOT IDENTIFY ANY CHANGES TO THE FLOOR FRAMING |
| | RECONFIGURATION? ADDITIONAL INFORMATION IS REQUIRED, |
| | 107.2.1.3. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION. |
| | |
| | 9) SHEET A2.1 HAS (3) AREAS WHERE WHITE OUT HAS BEEN |
| | USED ON THE PLANS. 107.2.1.4 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 EDITION 2012. QUALITY OF BUILDING |
| | PLANS. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. OTHER THAN THE |
| | RECONFIGURATION OF THE EXIT ENCLOSURE SHOWS NO WORK TO |
| | BE COMPLETED UNDERTHIS PERMIT. |
| | |
| | |
| | |
| | 10) STRUCTURAL SHEET S-1: |
| | |
| | 10A) STRUCTURAL SHEET ELEVATOR DETAIL IS MISSING THE |
| | FOLLOWING : |
| | 10A)(1) TB- HEIGTH NOT PROVIDED. |
| | 10A)(2) B-24 THE HEIGHT OF THE BEAM TOP OR BOTTOM OF |
| | BEAM NOT PROVIDED |
| | 10A)(3) ELEVATOR DOES NOT SHOW A PIT OR RECESS FOR THE |
| | FLOOR OF THE ELEVATOR CAB TO BE LEVEL WITH THE FLOOR. |
| | 10)(4) THE ELEVATOR SHAFT DOES NOT CONTINUE THROUGH THE |
| | SECOND FLOOR. |
| | 10)(5) SHAFT ENCLOSURE, 2010 FBC-B 708.12 ENCLOSURE AT |
| | THE TOP. A SHAFT ENCLOSURE THAT DOES NOT EXTEND TO THE |
| | UNDERSIDE OF THE ROOF SHEATHING, DECK OR SLAB OF THE |
| | BUILDING SHALL BE ENCLOSED AT THE TOP WITH CONSTRUCTION |
| | OF THE SAME FIRE-RESISTANCE RATING AS THE TOPMOST FLOOR |
| | PENETRATED BY THE SHAFT, BUT NOT LESS THAN THE |
| | FIRE-RESISTANCE RATING REQUIRED FOR THE SHAFT |
| | ENCLOSURE. |
| | |
| | |
| | 10B) STEEL COLUMNS & W 16X31 BEAM |
| | |
| | 10B)(1) PLANS CALL FOR 5X5X5/16 OR 5 INCH DIA X ).258 |
| | STEEL COLUMNS. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION 2012 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. |
| | |
| | 10B)(2) PLANS DO NOT PROVIDE THE SIZE FOR THE COLUMN |
| | BASE PLATE NOR TOP PLATE, THICKNESS, MATERIAL NOR THE |
| | BOLT LOCATION IN THE PLATE OR IF WELDED. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION, 2010 EDITION 2012 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS |
| | AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE |
| | FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. |
| | |
| | 10B)(3) NEW BATHROOM BEARING WALL DETAIL.DETAIL # 2 |
| | ONLY SHOWS THE BOTTOM OF THE STUD WALL DOES NOT |
| | INDICATE IF A SINGLE TOP PLATE IS REQUIRED OR IF DOUBLE |
| | TOP PLATE WILL BE REQUIRED? THE OTHER ISSUE IS WILL A |
| | STIFFNEER BE REQUIRED AS IN DETAIL # 3 FOR THE NEW |
| | CARRYING W 16X31 STEEL BEAM? IF SO WHAT TYPE OF |
| | MATERIALS AND NAILING PATTERN. |
| | |
| | 10C) FRONT ENTRY REDESIGN: |
| | 10C)(1) MISSING PRODUCT APPROVALS 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS:(31)(A) EXTERIOR DOORS. |
| | |
| | 10C)(2) MISSING DIMENSIONS, NO INFORMATION FOR VERTICAL |
| | NOR HORIZONTAL STEEL FRAMING MEMBERS, PRODUCT APPROVALS |
| | WILL NEED TO BE DECIDED TO BE ABLE TO PRODUCE THE |
| | SIZING OF THE ROUGH OPENING. 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 EDITION 107.2.1.3 ADDITIONAL DATA. |
| | THE BUILDING OFFICIAL MAY REQUIRE DETAILS, |
| | COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA NECESSARY |
| | TO DESCRIBE THE CONSTRUCTION OR INSTALLATION AND THE |
| | BASIS OF CALCULATIONS. ALL DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA REQUIRED BY THE BUILDING OFFICIAL TO |
| | BE PREPARED BY AN ARCHITECT OR ENGINEER SHALL BE |
| | AFFIXED WITH THEIR OFFICIAL SEAL, SIGNATURE AND DATE AS |
| | STATE LAW REQUIRES. |
| | |
| | |
| | 11) SHEET A3.1 DEATIL # 4 INDICATES THE INSTALATION OF |
| | DROP CEILINGS, NOTE # 6 INDICATES THE TYPE OF FASTENERS |
| | TO BE USED IF THE INSTALATION IS FOR CONCRETE DECKS BUT |
| | NOT FOR WOOD FRAMED TRUSSES WITH METAL HI HAT FRAMING |
| | BETWEEN THE 5/8 INCH DRYWALL AND FLOOR TRUSS. 2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1.3 |
| | ADDITIONAL DATA. |
| | |
| | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |