| Plan Review Notes For Permit 14030728 |
| Permit Number |
14030728 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-22 09:28:40 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) SPECIFY THE TYPE OF OCCUPANCY THAT THE GREASE TRAP | | | IS TO SERVICE AND PROVIDE SIZING CALCULATIONS AS | | | REQUIRED BY FBC PLUMBING 1003.5.3 ANS TABLE 1003.5.1. | | | | | | 2) THE DRAWINGS THAT WERE SUBMITTED HAVE LINES ACROSS | | | THEM AND ARE NOT CLEAR ENOUGH TO SCAN FOR PUBLIC | | | RECORD. SUBMIT CLEAN, CLEAR DRAWINGS AS REQUIRED BY | | | CITY AMENDMENTS 107.2.1.4 | | | | | | 3) SHOW THAT THE INLET DISCHARGE IS A MINIMUM OF 2.5" | | | ABOVE THE LIQUID LEVEL LINE. FBC PLUMBING 1003.5.3. | | | | | | 4) UNLESS THE LID OF THE GREASE TRAP IS TO BE AT GRADE | | | LEVEL, PROVIDE A DETAIL OF THE MANHOLES OVER THE INLET | | | AND OUTLETS AND SHOW THAT THEY ARE CAPABLE OF | | | WITHSTANDING VEHICULAR TRAFFIC LOADS. FBC PLUMBING | | | 1003.5 AND 1003.5.2 | | | | | | 5) SPECIFY THE DISTANCE FROM THE BUILDING TO THE TRAP | | | AND INDICATE IF SHORING WILL BE REQUIRED TO PROTECT THE | | | BUILDINGS FOUNDATION. CITY AMENDMENTS 107.2.1 | | | | | | 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | REVIEW COMMENT HAS BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|