2014-04-28 17:47:012010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS
 (MANUAL J CALCULATIONS) AS REQUIRED BY FBCR M1401.3.
 NOTE: THE EQUIPMENT SCHEDULE ON THE MECHANICAL PLANS
 MUST MATCH THE CALCULATIONS.
  