| Plan Review Notes For Permit 14030725 |
| Permit Number |
14030725 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-22 11:28:17 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS AS | | | REQUIRED BY FBCR M1401.3. NOTE: THE EQUIPMENT SCHEDULE | | | ON THE MECHANICAL PLANS MUST MATCH THE CALCULATIONS. | | | | | | 2) THE PLANS SHOW DUCT WORK IN THE CEILING. BASED ON | | | THE WALL SECTION ON SHEET 2, THIS STRUCTURE HAS A FLAT | | | ROOF AND A SINGLE ASSEMBLY ROOF/CEILING AND THE CEILING | | | HEIGHT IS SPECIFIED AS 8' 1" ON THE PLANS. THE DUCT | | | WORK WILL NEED TO BE INSTALLED IN A CHASE. PLEASE | | | CLARIFY. | | | | | | 3) THE PLANS SPECIFY THE AIR HANDLER LOCATED IN A | | | CLOSET ABOVE A STACKABLE WASHER/DRYER. THERE WILL NOT | | | BE ENOUGH ROOM TO INSTALL THE A/H AND HAVE IT | | | ACCESSIBLE FOR SERVICING. FBCR M1401.2 PLEASE CORRECT. | | | | | | 4) SPECIFY THE SIZE OF THE SUPPLY DUCT FOR THE | | | BATHROOM. NOTE: THE TRANSFER DUCT IS TO BE 1.5 TIMES | | | THE CROSS SECTIONAL AREA OF ALL THE DUCTS ENTERING THE | | | MASTER SUIT. FBC M1602.4 | | | | | | 5) SPECIFY THE LOCATION AND VENTING OF THE GAS WATER | | | HEATER. FBCR M1801 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|