Plan Review Notes
Plan Review Notes For Permit 14030725
Permit Number 14030725
Review Stop M
Sequence Number 1
Notes
Date Text
2014-03-22 11:28:172010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS AS
 REQUIRED BY FBCR M1401.3. NOTE: THE EQUIPMENT SCHEDULE
 ON THE MECHANICAL PLANS MUST MATCH THE CALCULATIONS.
  
 2) THE PLANS SHOW DUCT WORK IN THE CEILING. BASED ON
 THE WALL SECTION ON SHEET 2, THIS STRUCTURE HAS A FLAT
 ROOF AND A SINGLE ASSEMBLY ROOF/CEILING AND THE CEILING
 HEIGHT IS SPECIFIED AS 8' 1" ON THE PLANS. THE DUCT
 WORK WILL NEED TO BE INSTALLED IN A CHASE. PLEASE
 CLARIFY.
  
 3) THE PLANS SPECIFY THE AIR HANDLER LOCATED IN A
 CLOSET ABOVE A STACKABLE WASHER/DRYER. THERE WILL NOT
 BE ENOUGH ROOM TO INSTALL THE A/H AND HAVE IT
 ACCESSIBLE FOR SERVICING. FBCR M1401.2 PLEASE CORRECT.
  
 4) SPECIFY THE SIZE OF THE SUPPLY DUCT FOR THE
 BATHROOM. NOTE: THE TRANSFER DUCT IS TO BE 1.5 TIMES
 THE CROSS SECTIONAL AREA OF ALL THE DUCTS ENTERING THE
 MASTER SUIT. FBC M1602.4
  
 5) SPECIFY THE LOCATION AND VENTING OF THE GAS WATER
 HEATER. FBCR M1801
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]