| 2014-03-25 08:57:45 | PROVIDE LOAD CALCULATION IN COMPLIANCE WITH NEC 220 - | | | NUMEROUS SECTIONS | | | AIR CONDITIONING LOAD APPEARS TO EXCEED HEAT LOAD AND | | | MUST BE USED | | | GENERAL LIGHTING LOAD TO SHOW FLOOR AREA USED FOR THE | | | CALCULATION 220.12 | | | OTHER LOADS TO BE SHOWN AND CALCULATED AS PER 220.14 | | | SERVICE APPEARS TO BE INDICATED AS NEW, SHOW LOCATIONS | | | OF ALL EQUIPMENT ON BUILDINGS | | | OTHER NOTE INDICATES EXISTING AND ADDITION, SHOW LOAD | | | CALCULATION PER 220.16 | | | GROUNDING ELECTRODE SYSTEM(S) REQUIRED PER 250.50 | | | SHOW CONNECTION TO EACH ELECTRODE PRESENT PER 250.52 | | | SHOW LOCATION OF HANDHOLE OR RISER FOR FPL CONNECTION | | | THHN INSULATION IS NOT FOR WET LOCATION USE 310.13 | | | PROVIDE DETAILS OF METERMAIN COMBINATION, INCLUDING AIC | | | RATINGS 110.9 | | | LEVEL OF ALTERATION PER FBC-EB VOLUME IS CALLED OUT AS | | | LEVEL 2 | | | SMOKE ALARMS TO BE INDICATED ON DRAWINGS | | | FOR ALL NEW WORK OR THOSE AREAS IN THE WORK AREA: | | | GFCI REQUIRED PER 210.8 | | | ARC FAULT REQUIRED PER 210.12 | | | PROVIDE LOAD BALANCING PER 210.11 | | | CORRECTIONS ARE REQUIRED PRIOR TO CONTINUING REVIEW | | | |
|