| Date |
Text |
| 2014-03-22 10:00:12 | 2010 FBC |
| | |
| | ACCORDING TO CITY RECORDS, THIS BUILDING WAS |
| | CONSTRUCTED IN 1926 AS A GARAGE/APARTMENT. THESE PLANS |
| | HAVE NOT BEEN REVIEWED BY ZONING AT THE TIME OF THIS |
| | REVIEW. IT APPEARS THAT THE GARAGE PORTION OF THIS |
| | BUILDING MAY HAVE BEEN ILLEGALLY CONVERTED TO LIVING |
| | SPACE WITHOUT THE PROPER PERMITS OR INSPECTIONS. NOTE: |
| | ZONING MAY NOT ALLOW THIS STRUCTURE TO HAVE A KITCHEN |
| | OR BE USED AS A RENTAL UNIT. SEE ZONING REVIEW |
| | COMMENTS. |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY |
| | CALCULATIONS. |
| | |
| | 2) THE ENERGY CALCULATIONS SPECIFY THAT THE ENTIRE 669 |
| | SQFT STRUCTURE IS A CRAWL SPACE WITH R-19 INSULATION. |
| | ONE OF THE WALL SECTIONS ON SHEET 2 SHOWS A CRAWL SPACE |
| | AND THE OTHER SHOWS A SLAB. PLEASE CLARIFY. |
| | |
| | 3) SPECIFY THE LOCATION OF THE GAS WATER HEATER ON THE |
| | PLANS. |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R314 AND R315 FOR SMOKE AND |
| | CARBON MONOXIDE ALARMS. |
| | |
| | 5) SHOW COMPLIANCE WITH FBC R310 FOR EMERGENCY ESCAPE |
| | AND RESCUE OPENINGS AT SLEEPING ROOMS. |
| | |
| | 6) THE NEW WINDOWS ARE TAGGED "A" ON THE THE ELEVATIONS |
| | ON SHEET 1 AND "B" ON THE FLOOR PLANS ON SHEETS 2 AND |
| | 3. PLEASE CLARIFY. |
| | |
| | 7) THE WINDOW SCHEDULE ON SHEET 1, SPECIFIES 37" X 37" |
| | WINDOWS FOR "A". THE ELEVATIONS APPEAR TO SHOW LARGER |
| | HEIGHT WINDOWS. PLEASE CLARIFY. |
| | |
| | 8) THE WORK IS SPECIFIED AS A LEVEL 2 ALTERATION ON THE |
| | PLANS. SINCE THE WORK AREA EXCEEDS 50 PERCENT OF THE |
| | AREA OF THE BUILDING IT SHOULD BE CLASSIFIED AS A LEVEL |
| | 3 ALTERATION AND A CHANGE OF OCCUPANCY ( CONVERTING THE |
| | GARAGE TO LIVING AREA ). FBC EXISTING BUILDING SECTIONS |
| | 405 AND 406 |
| | |
| | 9) THE PRODUCT APPROVALS FOR THE NEW WINDOWS ARE NOT |
| | RATED FOR LARGE MISSILE IMPACT WHICH IS REQUIRED BY FBC |
| | R301.2.1.2. SUBMIT TWO COPIES OF PRODUCT APPROVALS AS |
| | REQUIRED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD. |
| | |
| | 10) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE TRUSS |
| | ANCHORS AND STRAPS SPECIFIED ON THE PLANS. DCA RULE |
| | 9N-3 |
| | |
| | 11) THE CITY DOES NOT HAVE A PERMIT RECORD THAT SHOWS |
| | THAT THE DOORS AND WINDOWS IN THIS BUILDING WERE |
| | REPLACED. IF THE DOORS AND WINDOWS THAT ARE SPECIFIED |
| | AS EXISTING WERE INSTALLED RECENTLY WITHOUT PERMITS OR |
| | INSPECTIONS, SUBMIT TWO SETS OF PRODUCT APPROVALS FOR |
| | THEM AND THE REQUIRED IMPACT PROTECTION DEVICES. DCA |
| | RULE 9N-3 |
| | |
| | |
| | 12) IN ORDER TO SPEED THE REVIEW TIME OF YOUR |
| | RE-SUBMITTAL, PLEASE SUBMIT A RESPONSE LETTER |
| | INDICATING HOW THE REVIEW COMMENTS HAVE BEEN ADDRESSED. |
| | |
| | |
| | |