| Plan Review Notes For Permit 14030723 |
| Permit Number |
14030723 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-09 15:45:46 | FIRST ELECTRICAL REVIEW FAILED; THE FOLLOWING | | | CORRECTIONS ARE REQUIRED: | | | FOR THE SERVICE | | | 1. SUBMIT A LARGER LEGIBLE SITE PLAN (A1) TO INDICATE | | | WHERE THE SERVICE WILL BE LOCATED. | | | 2. FAILED TO INDICATE THE METERS. | | | 3. PROVIDE CONDUCTOR SIZES FOR LINE SIDE TAP AND FOR | | | LOAD SIDE TO INDIVIDUAL UNITS. | | | 4. MISSING THE HOUSE METER AND CORRESPONDING PANEL FOR | | | COMMON AREA LIGHTING ETC. | | | TEMPORARY LIGHTING | | | 5. SUBMIT A LARGER LEGIBLE SITE PLAN (A1) TO INDICATE | | | THE SCOPE OF WORK FOR THE TEMPORARY LIGHTING. | | | NOTE: FOR OCCUPANCY EVEN IF JUST FOR DEMO/SHOWING AN | | | OPERABLE FIRE ALARM AND EMERGENCY LIGHTING. | | | FOR FURTHER QUESTIONS ON THIS REVIEW, CONTACT MIKE | | | ALBARRAN (561) 805-6718 |
|