2014-04-08 09:17:46REROOF SECOND BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- FASTENER WITHDRAWAL TEST (TAS 105) PROVIDED:
 A) THE TEST NEED TO BE CONDUCTED BY AN APPROVED TESTING
 AGENCY AS REQUIRED BY SEC. 1.2 OF TAS 105-11.
 INFORMATION SUBMITTED DOESN'T IDENTIFY THE APPROVED
 TESTING AGENCY.
  
 B) TEST REPORT SUBMITTED IS INCOMPLETE. THE TEST REPORT
 HAS TO PROVIDE ALL THE INFORMATION REQUIRED BY TAS
 105-11. SEE TAS 105-11 AND APPENDIX A, FIELD WITHDRAWAL
 RESISTANCE TEST RESULT REPORT FOR ALL THE REQUIRED
 INFORMATION.
  
 C) NUMBER OF TESTS SAMPLES NEED TO BE INCREASED BY 125%
 AS REQUIRED BY TAS 105-11 SEC. 8.3. REVISE AS REQUIRED.
  
 D) ENGINEER TO PROVIDE THE ENGINEERING FIRM CERTIFICATE
 OF AUTHORIZATION NUMBER ON EACH SHEET AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF
 FLORIDA ADMINISTRATIVE CODE.
  
  
 2- REVISE RAS 117 CALCULATIONS SUBMITTED:
 A) ENGINEER TO CLARIFY WHERE WAS THE FASTENER VALUE
 FY=333LBF FROM TAS 105 TAKEN FROM? SEC. 107.2.1.3 OF
 CITY AMENDMENTS TO FBC.
  
 ***NOTE: ANY ROOF EQUIPMENT REMOVAL OR RETROFIT ROOF
 DRAINS REQUIRE SEPARATE PERMITS.
  