| Plan Review Notes For Permit 14030687 |
| Permit Number |
14030687 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-04-08 09:17:46 | REROOF SECOND BUILDING REVIEW CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- FASTENER WITHDRAWAL TEST (TAS 105) PROVIDED: | | | A) THE TEST NEED TO BE CONDUCTED BY AN APPROVED TESTING | | | AGENCY AS REQUIRED BY SEC. 1.2 OF TAS 105-11. | | | INFORMATION SUBMITTED DOESN'T IDENTIFY THE APPROVED | | | TESTING AGENCY. | | | | | | B) TEST REPORT SUBMITTED IS INCOMPLETE. THE TEST REPORT | | | HAS TO PROVIDE ALL THE INFORMATION REQUIRED BY TAS | | | 105-11. SEE TAS 105-11 AND APPENDIX A, FIELD WITHDRAWAL | | | RESISTANCE TEST RESULT REPORT FOR ALL THE REQUIRED | | | INFORMATION. | | | | | | C) NUMBER OF TESTS SAMPLES NEED TO BE INCREASED BY 125% | | | AS REQUIRED BY TAS 105-11 SEC. 8.3. REVISE AS REQUIRED. | | | | | | D) ENGINEER TO PROVIDE THE ENGINEERING FIRM CERTIFICATE | | | OF AUTHORIZATION NUMBER ON EACH SHEET AS REQUIRED BY | | | CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF | | | FLORIDA ADMINISTRATIVE CODE. | | | | | | | | | 2- REVISE RAS 117 CALCULATIONS SUBMITTED: | | | A) ENGINEER TO CLARIFY WHERE WAS THE FASTENER VALUE | | | FY=333LBF FROM TAS 105 TAKEN FROM? SEC. 107.2.1.3 OF | | | CITY AMENDMENTS TO FBC. | | | | | | ***NOTE: ANY ROOF EQUIPMENT REMOVAL OR RETROFIT ROOF | | | DRAINS REQUIRE SEPARATE PERMITS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|