| Plan Review Notes For Permit 14030687 |
| Permit Number |
14030687 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-20 10:49:10 | REROOF BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- MODIFIED BITUMEN ROOF SYSTEM NOA 10-1230.06 | | | SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE | | | CURRENT NOA (2 COPIES) AS REQUIRED BY DCA RULE 9N-3. | | | VISIT THE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. | | | | | | 2- PROVIDE FASTENER WITHDRAWAL TEST (TAS 105) AS | | | REQUIRED BY GENERAL LIMITATION #6 OF NOA SUBMITTED. | | | SEC. 1609 OF 2010 FBC. | | | | | | 3- REVISE RAS 117 CALCULATIONS SUBMITTED: | | | A) ENGINEER NEEDS TO PROVIDE CALCULATIONS BASED ON THE | | | TAS 105 REPORT. SEE ITEM #2 ABOVE. | | | | | | B) ENGINEER TO REVISE CALCULATIONS BASED ON THE CURRENT | | | NOA. SEE ITEM #1 ABOVE. | | | | | | ***NOTE: ANY ROOF EQUIPMENT REMOVAL OR RETROFIT ROOF | | | DRAINS REQUIRE SEPARATE PERMITS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|