2014-03-20 10:49:10REROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- MODIFIED BITUMEN ROOF SYSTEM NOA 10-1230.06
 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE
 CURRENT NOA (2 COPIES) AS REQUIRED BY DCA RULE 9N-3.
 VISIT THE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
  
 2- PROVIDE FASTENER WITHDRAWAL TEST (TAS 105) AS
 REQUIRED BY GENERAL LIMITATION #6 OF NOA SUBMITTED.
 SEC. 1609 OF 2010 FBC.
  
 3- REVISE RAS 117 CALCULATIONS SUBMITTED:
 A) ENGINEER NEEDS TO PROVIDE CALCULATIONS BASED ON THE
 TAS 105 REPORT. SEE ITEM #2 ABOVE.
  
 B) ENGINEER TO REVISE CALCULATIONS BASED ON THE CURRENT
 NOA. SEE ITEM #1 ABOVE.
  
 ***NOTE: ANY ROOF EQUIPMENT REMOVAL OR RETROFIT ROOF
 DRAINS REQUIRE SEPARATE PERMITS.
  