| 2014-04-03 09:46:53 | ELECTRIC DENIED. PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY | | | SUBMITTAL COMPLIANT WITH FBC-E 103 | | | NEC 700.12 THE EMERGENCY AND EXIT LIGHTS MUST BE ON A | | | LOCAL LIGHTING CIRCUIT IN THE AREA THAT THEY SERVE | | | AHEAD OF THE SWITCH. THERE IS A CONFLICT ON THE PLANS | | | WITH REGARDS TO THIS ARTICLE IN THE NEC. THERE IS ONE | | | SPECIFIC CIRCUIT CALLED OUT ON THE PLANS IN THE | | | ELECTRICAL PANEL SCHEDULE FOR EXIT LIGHTIS ONLY, BUT | | | THERE ARE ALSO NOTES ON THE PLANS TO THE ARTICLE | | | REFFERENCED ABOVE. PLEASE MAKE THE CLARIFICATIONS AND | | | RESUBMIT. | | | | | | FOR ANY QUESTIONS OR COMMENTS REGARDING THIS PLAN | | | REVIEW PLEASE CONTACT DAVID HAYES, ELECTRICAL PLANS | | | EXAMINER, PX3421. I CAN BE AT 561-805-6717 OR AT | | | [email protected]. | | | |
|