Plan Review Notes
Plan Review Notes For Permit 14030582
Permit Number 14030582
Review Stop B
Sequence Number 4
Notes
Date Text
2015-02-02 13:48:32BUILDING REVIEW APPROVED WITH PROVISO:
 *1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) ENTRY DOOR SIZE AS SHOWN ON DOOR SCHEDULE. (OK.
 ROBERT BROWN APPORVED SITE SPECIFIC DOOR ON 6/17/15
 UNDER APPLICATION #15040967).
 B) SLIDING GLASS DOORS SIZES SPECIFIED FOR D106 AND
 D107 DOORS ON DOOR SCHEDULE.
 C) WINDOW SIZES FOR W5, W6, W7 AND W8 WINDOWS SHOWN ON
 WINDOW SCHEDULE.
 D) THERE WAS A NEW NOA SUBMITTED FOR CASEMENT WINDOWS.
 NOA 13-0129.25 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE.
 NEED TO PROVIDE CURRENT NOA.
  
 **2- ALL PRODUCT APPROVALS TO BE APPROVED BY THE
 DESIGNER OF RECORD.
  
 ***3- FLAT ROOF: ENGINEER TO REVISE THE RAS 117
 CALCULATIONS:
 A) EXPOSURE CATEGORY IS "D". B) DESIGN PRESSURES FOR
 PERIMETER AREA ARE INCORRECT (-11.2 ?). C) CLEARLY
 IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY AND BASE
 SHEET FASTENING OPTION FROM NOA SUBMITTED IS BEING
 CONSIDERED FOR THE CALCULATIONS. (ENGINEER TO READ SEC.
 8.1 OF RAS 117). D) CALCULATIONS SUBMITTED ARE NOT
 CLEAR. ENGINEER TO PROVIDE SEPARATE CALCULATIONS FOR
 THE PERIMETER AND CORNER AREAS. E) ENGINEER NOTED THAT
 "SPACING FALLS BELOW 4" WHICH IS MINIMUM" AND THEN
 ANOTHER NOTE SAYING "PERIMETER SPACING AND CORNER NEED
 TO BE SPACED 4" O.C.". THIS IS CONTRADICTORY. IF THE
 CALCULATIONS CALL FOR SPACING THAT FALLS BELOW 4", THEN
 HOW COME THE SPACING IS 4" O. C. ?. F) CLEARLY SPECIFY
 NAILING SPACING AT THE LAP AND NUMBER OF ROWS AND
 NAILING SPACING IN THE FIELD OF THE SHEET.
  
 ****4- PROVIDE CURRENT OPEN CELL INSULATION REPORT.
 REPORT SUBMITTED IS EXPIRED.
  
 *****5- SOIL TEST REPORT TO HAVE ENGINEER'S ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST.
  