| 2014-11-18 08:46:54 | |
| | 1- REVISE GARAGE FINISH FLOOR ELEVATION ON SHEET S1 TO |
| | MATCH FINISH FLOOR ELEVATION SHOWN ON SHEET A1. SEC. |
| | 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ENTRY DOOR SIZE AS SHOWN ON DOOR SCHEDULE. |
| | |
| | B) SLIDING GLASS DOORS SIZES SPECIFIED FOR D106 AND |
| | D107 DOORS ON DOOR SCHEDULE. |
| | |
| | C) WINDOW SIZES FOR W5, W6, W7 AND W8 WINDOWS SHOWN ON |
| | WINDOW SCHEDULE. |
| | |
| | D) THERE WAS A NEW NOA SUBMITTED FOR CASEMENT WINDOWS. |
| | NOA 13-0129.25 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. |
| | NEED TO PROVIDE CURRENT NOA. |
| | |
| | 3- ALL PRODUCT APPROVALS TO BE APPROVED BY THE DESIGNER |
| | OF RECORD. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 4- FLAT ROOF: ENGINEER TO REVISE THE RAS 117 |
| | CALCULATIONS: |
| | A) EXPOSURE CATEGORY IS NOT "B" OR "C". SEE PLANS AND |
| | REVISE AS REQUIRED. SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| | B) DESIGN PRESSURES FOR PERIMETER AREA ARE INCORRECT |
| | (-11.2 ?). |
| | C) CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY |
| | AND BASE SHEET FASTENING OPTION FROM NOA SUBMITTED IS |
| | BEING CONSIDERED FOR THE CALCULATIONS. (ENGINEER TO |
| | READ SEC. 8.1 OF RAS 117). |
| | D) CALCULATIONS SUBMITTED ARE NOT CLEAR. ENGINEER TO |
| | PROVIDE SEPARATE CALCULATIONS FOR THE PERIMETER AND |
| | CORNER AREAS. |
| | E) ENGINEER NOTED THAT "SPACING FALLS BELOW 4" WHICH IS |
| | MINIMUM" AND THEN ANOTHER NOTE SAYING "PERIMETER |
| | SPACING AND CORNER NEED TO BE SPACED 4" O.C.". THIS IS |
| | CONTRADICTORY. IF THE CALCULATIONS CALL FOR SPACING |
| | THAT FALLS BELOW 4", THEN HOW COME THE SPACING IS 4" O. |
| | C. ? |
| | F) CLEARLY SPECIFY NAILING SPACING AT THE LAP AND |
| | NUMBER OF ROWS AND NAILING SPACING IN THE FIELD OF THE |
| | SHEET. |
| | |
| | 5- PROVIDE CURRENT OPEN CELL INSULATION REPORT. REPORT |
| | SUBMITTED IS EXPIRED. |
| | |
| | 6- SOIL TEST REPORT TO HAVE ENGINEER'S ORIGINAL |
| | SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST. |
| | |
| | 7- OWNER/AGENT TO SIGN AND DATE THE ENERGY |
| | CALCULATIONS. SEC. 103.2.3.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | |
| | NOTES: |
| | *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REPLACE ALL REVISED SHEETS. |
| | *** APPLY FOR LANDSCAPE AND IRRIGATION UNDER SEPARATE |
| | PERMITS. |
| | *** ELEVATION CERTIFICATES REQUIRED DURING |
| | CONSTRUCTION. |
| | |
| | |