Date Text
2014-11-18 08:46:54 
 1- REVISE GARAGE FINISH FLOOR ELEVATION ON SHEET S1 TO
 MATCH FINISH FLOOR ELEVATION SHOWN ON SHEET A1. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ENTRY DOOR SIZE AS SHOWN ON DOOR SCHEDULE.
  
 B) SLIDING GLASS DOORS SIZES SPECIFIED FOR D106 AND
 D107 DOORS ON DOOR SCHEDULE.
  
 C) WINDOW SIZES FOR W5, W6, W7 AND W8 WINDOWS SHOWN ON
 WINDOW SCHEDULE.
  
 D) THERE WAS A NEW NOA SUBMITTED FOR CASEMENT WINDOWS.
 NOA 13-0129.25 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE.
 NEED TO PROVIDE CURRENT NOA.
  
 3- ALL PRODUCT APPROVALS TO BE APPROVED BY THE DESIGNER
 OF RECORD. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- FLAT ROOF: ENGINEER TO REVISE THE RAS 117
 CALCULATIONS:
 A) EXPOSURE CATEGORY IS NOT "B" OR "C". SEE PLANS AND
 REVISE AS REQUIRED. SEC. R301 OF 2010 FBC-RESIDENTIAL.
 B) DESIGN PRESSURES FOR PERIMETER AREA ARE INCORRECT
 (-11.2 ?).
 C) CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY
 AND BASE SHEET FASTENING OPTION FROM NOA SUBMITTED IS
 BEING CONSIDERED FOR THE CALCULATIONS. (ENGINEER TO
 READ SEC. 8.1 OF RAS 117).
 D) CALCULATIONS SUBMITTED ARE NOT CLEAR. ENGINEER TO
 PROVIDE SEPARATE CALCULATIONS FOR THE PERIMETER AND
 CORNER AREAS.
 E) ENGINEER NOTED THAT "SPACING FALLS BELOW 4" WHICH IS
 MINIMUM" AND THEN ANOTHER NOTE SAYING "PERIMETER
 SPACING AND CORNER NEED TO BE SPACED 4" O.C.". THIS IS
 CONTRADICTORY. IF THE CALCULATIONS CALL FOR SPACING
 THAT FALLS BELOW 4", THEN HOW COME THE SPACING IS 4" O.
 C. ?
 F) CLEARLY SPECIFY NAILING SPACING AT THE LAP AND
 NUMBER OF ROWS AND NAILING SPACING IN THE FIELD OF THE
 SHEET.
  
 5- PROVIDE CURRENT OPEN CELL INSULATION REPORT. REPORT
 SUBMITTED IS EXPIRED.
  
 6- SOIL TEST REPORT TO HAVE ENGINEER'S ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST.
  
 7- OWNER/AGENT TO SIGN AND DATE THE ENERGY
 CALCULATIONS. SEC. 103.2.3.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
  
 NOTES:
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE ALL REVISED SHEETS.
 *** APPLY FOR LANDSCAPE AND IRRIGATION UNDER SEPARATE
 PERMITS.
 *** ELEVATION CERTIFICATES REQUIRED DURING
 CONSTRUCTION.
  
  