| 2014-08-18 15:19:41 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: 2010 FBC. |
| | |
| | 1- REVISE GARAGE FINISH FLOOR ELEVATION ON SHEET S1. |
| | SEE REVISED FINISH ELEVATIONS ON SHEET A1. SEC. 107.2.1 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 2- ARCHITECT'S PLANS CALL FOR NAPOLEON LHD45, WHICH IS |
| | A DIRECT VENT GAS FIREPLACE. FIREPLACE SPECS SUBMITTED |
| | ARE FOR A LENNOX WOOD BURNING FIREPLACE. ARCHITECT TO |
| | REVIEW AND APPROVE SPECS SUBMITTED AND REVISE PLANS AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- SHEET A2: NEED EGRESS FOR DEN/BEDROOM. SEC. R310 ( |
| | OR CLEARLY REVISE NOTE TO STATE THAT THE DEN CAN NOT BE |
| | USED FOR SLEEPING PURPOSES. NOTE: IS NOT CLEAR THE WAY |
| | IT WAS WRITTEN.). SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- REVISE OVERFLOW DETAIL B/A15. DETAIL SUBMITTED |
| | DOESN'T SHOW THE OVERFLOW SCUPPER. SEC. R903.4.1. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ALUMINUM CURTAIN WALL SYSTEM: NOA 12-1005.03 |
| | SUBMITTED IS SMALL MISSILE IMPACT RESISTANT. NEED LARGE |
| | MISSILE IMPACT RESISTANT OR PROVIDE SHUTTERS. SEC. |
| | R301.2.1.2 OF 2010 FBC-RESIDENTIAL. AND, CLEARLY |
| | IDENTIFY WINDOWS AND MULLIONS SIZES. |
| | |
| | B) SHUTTERS IF NOT SUBMITTING WINDOW ASSEMBLIES FOR |
| | LARGE MISSILE IMPACT. AND PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEC. R301.2.1.2. |
| | |
| | C) ENTRY DOOR COMPLETE ASSEMBLY AND SIZE AS SHOWN ON |
| | PLANS. NOA 13-0617.29 SUBMITTED DOESN'T COVER SIZE |
| | SHOWN ON ELEVATION. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | FRAMING PLANS/ DETAILS AND SPECIFICATIONS. ONLY |
| | SUBMITTED FLORIDA PRODUCT APPROVALS ON THE TRUSS STRAP |
| | SCHEDULE ON SHEET S3. NEED TO PROVIDE CURRENT 2010 CODE |
| | PRODUCT APPROVALS. FL3750 IS NOT CURRENT. AND NEED |
| | PRODUCT APPROVALS FOR CONNECTORS SPECIFIED ON ALL |
| | DETAILS. |
| | |
| | E) FLAT ROOF: PROVIDE COMPLETE NOA. ONLY PAGES 15 AND |
| | 16 WERE SUBMITTED. |
| | |
| | F) SLIDING GLASS DOORS. PROVIDE PRODUCT APPROVAL FOR |
| | 12'-0" SIZES SHOWN ON PLANS. NOA 12-0130.12 SUBMITTED |
| | DOESN'T COVER D107 DOOR SIZE. |
| | |
| | G) WINDOWS W5, W6, W7 AND W8. NEED PRODUCT APPROVAL |
| | THAT COVERS SIZE SPECIFIED ON PLANS FOR THIS WINDOWS. |
| | NOA 13-0115.04 SUBMITTED DOESN'T COVER THESE SIZES. |
| | |
| | 6- ALL PRODUCT APPROVALS TO BE APPROVED IN WRITING (NOT |
| | SIGNING AND SEALING) BY THE STRUCTURAL ENGINEER OF |
| | RECORD. SEC. 107.3.4.1 CITY AMENDMENTS. PLEASE, |
| | IDENTIFY WHO'S APPROVING ALL THE PRODUCT APPROVALS. |
| | |
| | 7- ENGINEER TO REVISE RAS 117 CALCULATIONS. SEE PLANS |
| | AND REVISE. SEC. 107.2.1 CITY AMENDMENTS: |
| | A) BUILDING HEIGHT. |
| | |
| | B) ROOF ANGLE IS NOT 25 DEG. SEE PLANS. |
| | |
| | C) EXPOSURE CATEGORY IS NOT "B". SEE PLANS. |
| | |
| | D) 3" NAIL SPACING FOR ROOF ZONE 3 IS NOT ALLOWED. SEE |
| | RAS 117 SEC. 8.1 AND REVISE AS REQUIRED. |
| | |
| | E) CLEARLY SPECIFY NAILING AT THE LAP AND NUMBER OF |
| | ROWS AND NAILING SPACING IN THE FIELD. |
| | |
| | F) BASE SHEET FASTENING OPTION HIGHLIGHTED ON THE NOA |
| | SUBMITTED DOESN'T MATCH SYSTEM SPECIFIED BY THE |
| | ENGINEER. REVISE AS REQUIRED TO MATCH. |
| | |
| | 8- PROVIDE CURRENT OPEN CELL INSULATION REPORT. |
| | ESR-3102 REPORT SUBMITTED IS EXPIRED. AND, REVISE PLANS |
| | TO MATCH SPECIFIC TYPE OF INSULATION SUBMITTED. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 9- DESIGNER OF RECORD TO PROVIDE SPECS AND DETAILS FOR |
| | TILE VENEER INSTALLATION AS PART OF THE SITE SPECIFIC |
| | INSTALLATION IN THIS HOUSE. INSTALLATION SHALL MEET THE |
| | WIND LOAD REQUIREMENTS OF SEC. R301 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 10- ENERGY CALCULATIONS SUBMITTED: COORDINATE |
| | INFORMATION WITH PLANS AND PRODUCT APPROVALS SUBMITTED. |
| | SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION: |
| | A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC. |
| | 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | B) REVISE AND PROVIDE COMPLETE INFORMATION ON TOP OF |
| | FORM, ADDRESS IS 125 CHURCHILL RD NOT 101, PERMIT |
| | OFFICE IS WEST PALM BEACH NOT PALM BEACH COUNTY. AND, |
| | PROVIDE THE JURISDICTION NUMBER. |
| | |
| | C) REVISE MATERIAL OF ROOF SPECIFIED ON PAGE 2 OF 6. |
| | IT'S NOT CONCRETE. SEE PLANS. |
| | |
| | D) REVISE INFORMATION FOR DOORS ON SHEET 3 OF 6. SEE |
| | PLANS AND PRODUCT APPROVALS SUBMITTED. ***NOTE: DOOR |
| | NEEDS TO BE COUNTED AS GLAZING. SEE SEC. 405.5.3 OF |
| | 2010 FBC-ENERGY CONSERVATION |
| | |
| | 11- SOIL TEST REPORT SUBMITTED IS INCOMPLETE. REPORT |
| | NEEDS TO PROVIDE ALL THE INFORMATION REQUIRED BY SEC. |
| | 1803.6 OF 2010 FBC. REVIEW THIS SECTION AND PROVIDE ALL |
| | THE INFORMATION. RESUBMIT TWO SIGNED AND SEALED COPIES. |
| | |
| | |
| | NOTES: |
| | *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REPLACE ALL REVISED SHEETS. |
| | *** APPLY FOR LANDSCAPE AND IRRIGATION UNDER SEPARATE |
| | PERMITS. |
| | *** ELEVATION CERTIFICATES REQUIRED DURING |
| | CONSTRUCTION. |
| | |
| | |