2014-08-18 15:19:41NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: 2010 FBC.
  
 1- REVISE GARAGE FINISH FLOOR ELEVATION ON SHEET S1.
 SEE REVISED FINISH ELEVATIONS ON SHEET A1. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 2- ARCHITECT'S PLANS CALL FOR NAPOLEON LHD45, WHICH IS
 A DIRECT VENT GAS FIREPLACE. FIREPLACE SPECS SUBMITTED
 ARE FOR A LENNOX WOOD BURNING FIREPLACE. ARCHITECT TO
 REVIEW AND APPROVE SPECS SUBMITTED AND REVISE PLANS AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- SHEET A2: NEED EGRESS FOR DEN/BEDROOM. SEC. R310 (
 OR CLEARLY REVISE NOTE TO STATE THAT THE DEN CAN NOT BE
 USED FOR SLEEPING PURPOSES. NOTE: IS NOT CLEAR THE WAY
 IT WAS WRITTEN.). SEC. 107.2.1 CITY AMENDMENTS.
  
 4- REVISE OVERFLOW DETAIL B/A15. DETAIL SUBMITTED
 DOESN'T SHOW THE OVERFLOW SCUPPER. SEC. R903.4.1.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALUMINUM CURTAIN WALL SYSTEM: NOA 12-1005.03
 SUBMITTED IS SMALL MISSILE IMPACT RESISTANT. NEED LARGE
 MISSILE IMPACT RESISTANT OR PROVIDE SHUTTERS. SEC.
 R301.2.1.2 OF 2010 FBC-RESIDENTIAL. AND, CLEARLY
 IDENTIFY WINDOWS AND MULLIONS SIZES.
  
 B) SHUTTERS IF NOT SUBMITTING WINDOW ASSEMBLIES FOR
 LARGE MISSILE IMPACT. AND PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEC. R301.2.1.2.
  
 C) ENTRY DOOR COMPLETE ASSEMBLY AND SIZE AS SHOWN ON
 PLANS. NOA 13-0617.29 SUBMITTED DOESN'T COVER SIZE
 SHOWN ON ELEVATION.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS/ DETAILS AND SPECIFICATIONS. ONLY
 SUBMITTED FLORIDA PRODUCT APPROVALS ON THE TRUSS STRAP
 SCHEDULE ON SHEET S3. NEED TO PROVIDE CURRENT 2010 CODE
 PRODUCT APPROVALS. FL3750 IS NOT CURRENT. AND NEED
 PRODUCT APPROVALS FOR CONNECTORS SPECIFIED ON ALL
 DETAILS.
  
 E) FLAT ROOF: PROVIDE COMPLETE NOA. ONLY PAGES 15 AND
 16 WERE SUBMITTED.
  
 F) SLIDING GLASS DOORS. PROVIDE PRODUCT APPROVAL FOR
 12'-0" SIZES SHOWN ON PLANS. NOA 12-0130.12 SUBMITTED
 DOESN'T COVER D107 DOOR SIZE.
  
 G) WINDOWS W5, W6, W7 AND W8. NEED PRODUCT APPROVAL
 THAT COVERS SIZE SPECIFIED ON PLANS FOR THIS WINDOWS.
 NOA 13-0115.04 SUBMITTED DOESN'T COVER THESE SIZES.
  
 6- ALL PRODUCT APPROVALS TO BE APPROVED IN WRITING (NOT
 SIGNING AND SEALING) BY THE STRUCTURAL ENGINEER OF
 RECORD. SEC. 107.3.4.1 CITY AMENDMENTS. PLEASE,
 IDENTIFY WHO'S APPROVING ALL THE PRODUCT APPROVALS.
  
 7- ENGINEER TO REVISE RAS 117 CALCULATIONS. SEE PLANS
 AND REVISE. SEC. 107.2.1 CITY AMENDMENTS:
 A) BUILDING HEIGHT.
  
 B) ROOF ANGLE IS NOT 25 DEG. SEE PLANS.
  
 C) EXPOSURE CATEGORY IS NOT "B". SEE PLANS.
  
 D) 3" NAIL SPACING FOR ROOF ZONE 3 IS NOT ALLOWED. SEE
 RAS 117 SEC. 8.1 AND REVISE AS REQUIRED.
  
 E) CLEARLY SPECIFY NAILING AT THE LAP AND NUMBER OF
 ROWS AND NAILING SPACING IN THE FIELD.
  
 F) BASE SHEET FASTENING OPTION HIGHLIGHTED ON THE NOA
 SUBMITTED DOESN'T MATCH SYSTEM SPECIFIED BY THE
 ENGINEER. REVISE AS REQUIRED TO MATCH.
  
 8- PROVIDE CURRENT OPEN CELL INSULATION REPORT.
 ESR-3102 REPORT SUBMITTED IS EXPIRED. AND, REVISE PLANS
 TO MATCH SPECIFIC TYPE OF INSULATION SUBMITTED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 9- DESIGNER OF RECORD TO PROVIDE SPECS AND DETAILS FOR
 TILE VENEER INSTALLATION AS PART OF THE SITE SPECIFIC
 INSTALLATION IN THIS HOUSE. INSTALLATION SHALL MEET THE
 WIND LOAD REQUIREMENTS OF SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 10- ENERGY CALCULATIONS SUBMITTED: COORDINATE
 INFORMATION WITH PLANS AND PRODUCT APPROVALS SUBMITTED.
 SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) REVISE AND PROVIDE COMPLETE INFORMATION ON TOP OF
 FORM, ADDRESS IS 125 CHURCHILL RD NOT 101, PERMIT
 OFFICE IS WEST PALM BEACH NOT PALM BEACH COUNTY. AND,
 PROVIDE THE JURISDICTION NUMBER.
  
 C) REVISE MATERIAL OF ROOF SPECIFIED ON PAGE 2 OF 6.
 IT'S NOT CONCRETE. SEE PLANS.
  
 D) REVISE INFORMATION FOR DOORS ON SHEET 3 OF 6. SEE
 PLANS AND PRODUCT APPROVALS SUBMITTED. ***NOTE: DOOR
 NEEDS TO BE COUNTED AS GLAZING. SEE SEC. 405.5.3 OF
 2010 FBC-ENERGY CONSERVATION
  
 11- SOIL TEST REPORT SUBMITTED IS INCOMPLETE. REPORT
 NEEDS TO PROVIDE ALL THE INFORMATION REQUIRED BY SEC.
 1803.6 OF 2010 FBC. REVIEW THIS SECTION AND PROVIDE ALL
 THE INFORMATION. RESUBMIT TWO SIGNED AND SEALED COPIES.
  
  
 NOTES:
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE ALL REVISED SHEETS.
 *** APPLY FOR LANDSCAPE AND IRRIGATION UNDER SEPARATE
 PERMITS.
 *** ELEVATION CERTIFICATES REQUIRED DURING
 CONSTRUCTION.
  
  