2014-05-13 16:37:01NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: 2010 BC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY ( 2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROPERTY IS LOCATED IN FLOOD ZONE A5. EELEVATION
 CERTIFICATES WILL BE REQUIRED DURING CONSTRUCTION. SEC.
 R322.
  
 3- FLOOD ZONE A5 WITH BASE FLOOD LEVATION OF 7'-0".
 CITY FLOODPLAIN MANAGEMENT POLICY ARTICLE XVII REQUIRES
 THE LOWEST FLOOR TO BE RAISED 6" ABOVE BASE FLOOR
 ELEVATION. FOUNDATION AND FLOOR PLANS SHOW FINISH FLOOR
 ELEVATION OF 8'-0" FOR THE MAIN HOUSE AND 7'-6" FOR THE
 GARAGE. GARAGE FLOOR IS TYPICALLY SLOPED DOWN TO THE
 ENTRY TO ALLOW FOR WATER TO RUN OFF. THIS WILL REDUCE
 THE FINISH FLOOR ELEVATION OF THE GARAGE BELOW THE
 REQUIRED 6" . CLEARLY IDENTIFY ON PLANS THE GARAGE
 LOWEST FINISH FLOOR OF THE GARAGE AT ENTRY POINT.
 OTHERWISE, LESS THAN 7'-6" ELEVATION WILL REQUIRE FLOOD
 RESISTANT CONSTRUCTION. SEC. R322.
  
 4- FIREPLACE: PROVIDE MANUFACTURER SPECS. SEC. R1004,
 R1005.
  
 5- IRRIGATION, LANDSCAPE, FENCES, POOLS, GAS ARE
 SEPARATE PERMITS. SUBMIT APPLICATIONS AND DRAWINGS
 UNDER SEPARATE PERMITS. SEC 107.2.1.4 CITY AMENDMENTS
 TO FBC.
  
 6- A) PROVIDE SITE DRAINAGE PLAN TO SHOW COMPLIANCE
 WITH SEC. R401.3.
  
 B) SHEET SP1: WHERE IS THE DECK DRAIN (BY MASTER
 BEDROOM AND LOGGIA) DRAINING TO. SEC. R401.3.
  
 7- SHEET S1:
 A) DETAIL 8/S1. FOOTING SIZE 2' OR 20". REVISE AS
 REQUIRED TO MATCH. ALSO, SEE THE ANALYSIS AND
 RECOMMENDATIONS OF SOIL TEST REPORT BY NETTING
 ENGINEERS FOR FOOTING SIZE RECOMMENDATIONS. THEY
 RECOMMEND 24" MIN. ENGINEER OF RECORD TO PROVIDE
 RESPONSE IN WRITING EXPLAINING WHY DESIGNING A SMALLER
 FOOTING?. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 B) DESIGN PRESSURES FOR DOORS AND WINDOWS DON'T
 CORRESPOND TO EXPOSURE "D" ACCORDING TO THE SIZE AND
 LOCATION. REVISE AS REQUIRED OR PROVIDE CALCULATIONS
 SHOWING THE CALCULATED DESIGN PRESSURES. SEC. R301.1
 FBC-RESIDENTIAL AND SEC. 107.2.1.3 CITY AMENDMENTS TO
 FBC.
 **NOTE: THIS APPLIES TO OPENINGS DESIGN PRESSURES ON
 SHEET S2 AND THE COMPONENTS AND CLADDING DESIGN
 PRESSURES ON SHEET S5. REVISE AS REQUIRED TO MATCH.
  
 8- SHEET S3: ROOF SHEATHING ATTACHMENT SPECIFICATIONS
 ON DETAIL 9/S3 DON'T MATCH SPECS SHOWN ON PLYWOOD
 BLOCKING DETAIL 1/S5 ON SHEET S5. REVISE TO MATCH.
 (NOTE: NEED TO SPECIFY RING SHANK NAILS AS REQUIRED BY
 SEC. R803.2.3.1.)
  
 9- SHEET A2:
 A) NEED EGRESS FOR DEN/BEDROOM AS REQUIRED BY SEC. R310
 ( OR CLEARLY IDENTIFY ON PLANS THAT THE DEN CAN'T NOT
 BE USED FOR SLEEPING PURPOSES).
  
 B) ROOF NEED OVERFLOW SCUPPERS AS REQUIRED BY SEC.
 R903.4.1. NOTE: SEE SEC. R903.4.1 FOR REQUIRED
 LOCATION.
  
 10- SHEET A3: A) SPECIFY OVERFLOW SCUPPERS FOR ALL ROOF
 AREAS. SEE SEC. R903.4.1.
  
 B) REVISE EMERGENCY OVERFLOW SCUPPER LOCATION SHOWN ON
 PLAN. SEC. R903.4.1
  
 C) REVISE NOTE. THEY NEED TO BE CLOSE TO THE PARAPET
 SCUPPERS. SEE SEC. R903.4.1.
  
 11- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL STOREFRONT ASSEMBLIES AS SHOWN ON PLANS AND
 ELEVATIONS. OR, PROVIDE COMPLETE ENGINEERING PACKAGE
 AND APPLY FOR SITE SPECIFIC PRODUCT APPROVAL.
  
 B) ENTRY DOOR COMPLETE ASSEMBLY AND SIZE AS SHOWN ON
 PLANS.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 D)FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7.
 PROVIDE COMPLETE NOA. ONLY THE PAGE SHOWING THE
 SELECTED ASSEMBLY WAS SUBMITTED. NEED FIRST PAGES
 SHOWING ALL THE COMPONENTS AND LAST PAGE SHOWING THE
 LIMITATIONS.
  
 E) SLIDING GLASS DOORS. PROVIDE PRODUCT APPROVAL FOR
 DOORS THAT MATCH SIZES SHOWN ON PLANS AND ASSEMBLIES
 SHOWN ON PLANS AND ELEVATIONS.
 ALSO, NOA 11-1018.14 SUBMITTED DOESN'T COVER SIZES
 SHOWN ON PLANS AND WAS SUPERSEDED BY MIAMI-DADE. VISIT
 THE MIAMI-DADE WEBSITE DOWNLOAD CURRENT NOA AND
 RESUBMIT 2 NEW COPIES.
  
 F) WINDOW W6. NEED PRODUCT APPROVAL THAT COVERS SIZE
 SPECIFIED ON PLANS FOR THIS WINDOW.
  
 12- ALL PRODUCT APPROVALS TO BE REVIEWED AND APPROVED
 IN WRITING (NOT SIGNING AND SEALING) BY THE ENGINEER OR
 ARCHITECT OF RECORD. SEC. 107.3.4.1 CITY AMENDMENTS.
 PACKAGE SUBMITTED WAS NOT REVIEWED BY EITHER ONE.
 PLEASE, IDENTIFY WHO'S APPROVING ALL THE PRODUCT
 APPROVALS.
  
 13- PROVIDE ICYNENE INSULATION MANUFACTURER'S SPECS
 SHOWING COMPLIANCE WITH SEC. R316.
  
 14- SHEET A13 WALL SECTIONS: SPECIFY FIREBLOCKING IN
 ALL CONCEALED SPACES AS REQUIRED BY SEC. R 302.11.
  
 15- SHEET A14:
 A) PROVIDE SPECS/DETAILS FOR STAIRS OPEN RISERS TO SHOW
 COMPLIANCE WITH SEC. R311.7.4.3
  
 B) STAIR GUARDRAIL TO COMPLY WITH THE OPENING
 LIMITATION OF SEC. R312.3
  
 C) SPECIFY FIREBLOCKING IN ALL CONCEALED SPACES AS
 REQUIRED BY SEC. R302.11.
  
 16- PROVIDE SPECS AND DETAILS FOR TILE VENEER
 INSTALLATION. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 17- SPECIFY CARBON MONOXIDE ALARMS AS REQUIRED BY SEC.
 R315.
  
 18- SOIL TEST REPORT SUBMITTED: NEED ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE. CHAPTER 471 FLORIDA
 STATUTE.
  
 19- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER, BUILDER, PERMIT OFFICE, ETC. SEC.
 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) REVISE TYPE AND MATERIAL OF ROOF SPECIFIED ON PAGE 2
 OF 6. THIS IS A FLAT ROOF NOT HIP.
  
 D) REVISE DOOR TYPE SPECIFIED ON PAGE 3 OF 6. THERE ARE
 NO WOOD DOORS. SEE PLANS AND PRODUCT APPROVALS
 SUBMITTED.
  
 E) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION ON
 PAGE 3 OF 6 TO MATCH PLANS AND ELEVATIONS SUBMITTED..
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***SEE ZONING COMMENTS. NEED RECORDED PLAT.
 *** ELEVATION CERTIFICATES REQUIRED DURING
 CONSTRUCTION.
 *** NEED NEW ADDRESS FOR EACH LOT WHEN LOT SUBDIVISION
 IS RECORDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL