| Plan Review Notes For Permit 14030573 |
| Permit Number |
14030573 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-14 15:58:58 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED IN A 170 MPH VULT WIND | | | SPEED AND THE EXPOSURE CATEGORY IS C. THE MAXIMUM | | | DESIGN PRESSURE FOR THE SELECTED ROOFING ASSEMBLY ON | | | PAGE 22 IS -60 PSF. THIS PRESSURE IS NOT ADEQUATE FOR | | | THE PERIMETER AND CORNER ROOF AREA. SUBMIT TWO SETS OF | | | RAS 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED | | | BY LIMITATION NUMBER 7 ON PAGE 26 OF THE PRODUCT | | | APPROVAL. FBC R301.2.1T | | | | | | 2) THERE IS A PRODUCT APPROVAL FOR BORAL TILESEAL (NOA | | | NO.12-1219.01) ATTACHED TO THE POLYGLASS SELF ADHERED | | | ROOF SYSTEM FOR THE FLAT DECKS. THIS PRODUCT CAN NOT BE | | | USED WITH THE POLY GLASS SELF-ADHERED ON THE FLAT DECK, | | | IT IS NOT LISTED AS PART OF THE ASSEMBLY. THE TILE SEAL | | | NOA SPECIFIES THE SURFACING MATERIALS THAT IS APPROVED | | | FOR ON PAGE 3 OF 4. PLEASE CLARIFY WHERE THE BORAL | | | TILESEAL WILL BE INSTALLED. | | | | | | 3) SPECIFY THE ROOF SLOPE AND THE MEAN ROOF HEIGHT ON | | | THE APPLICATION OR PLANS. CITY AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|