| 2014-06-06 17:42:45 | BUILDING PLAN REVIEW |
| | PERMIT: 14030562 |
| | ADD: 1875 PALM BCH LAKES # A09 |
| | CONT: TO BE DETERMINED |
| | TEL: (561)373-3902 / KARI |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: FRIDAY JUNE 06/2014 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) PB OUTLET MALLS: |
| | A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| | CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT |
| | CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| | PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND |
| | NOTARIZED. |
| | |
| | 3A) COMPLIED. |
| | |
| | 3B) NOTE TO DESIGNER!!!: CHAPTER 553.80(2)(B) FLORIDA |
| | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED THREE OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | 2ND REQUEST!!!THE PLANS, LIFE SAFETY SHEET A1.0 ARE |
| | INDICATING THEY ARE TAKING AREA INCREASES FOR FIRE |
| | SPRINKLERS, THE INDEX AND PLANS FAIL TO CONTAIN FIRE |
| | SPRINKLER & FIRE ALARM PLANS WITHIN THIS SET. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | (5) . FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | SCHEMATIC FIRE SPRINKLERSFIRE SPRINKLER PLANS ARE A |
| | MUST, OVER 12,000 SQ FT. SHEET A1.0 INDICATE A AREA |
| | INCREASE OF 300% WITH |
| | FIRE SPRINKLERS, THERE ARE NO FIRE SPRINKLER PLANS |
| | LISTED IN THE INDEX NOR IS THERE A SEPARATE SET OF FIRE |
| | SPRINKLER PLANS SUBMITTED WITH THE 2ND SUBMITTAL. |
| | |
| | SECTION NOT MET: 2010 FBC-B F] 903.2.7 GROUP M. AN |
| | AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT |
| | BUILDINGS CONTAINING A GROUP M OCCUPANCY WHERE ONE OF |
| | THE FOLLOWING CONDITIONS EXISTS: 1. A GROUP M FIRE AREA |
| | EXCEEDS 12,000 SQUARE FEET (1115 M2). |
| | |
| | 3C) COMPLIED. |
| | |
| | 4) 2ND REQUEST, BUILDING EVALUATION IS STILL LOW. THE |
| | ICC TABLES PUT THE BUILDING TYPE IIB AT $115.47 SQ FT. |
| | THE SHELL' |
| | ROOF & FIRE SPRINKLERS TOTAL COST COMES TO $44.00 A |
| | SQUARE FOOT OR THE TENANT BUILD OUT WITH THE FIRE |
| | SPRINKLERS FOR THE TENANT BUILD OUT INCLUDED AT $71.00 |
| | A SQUARE FOOT. |
| | THE TENANT BUILD OUT VALUE IS LOW AT $18.64 DOLLARS / |
| | SQ FT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF |
| | PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 5-7) COMPLIED. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |