| Date |
Text |
| 2014-04-14 17:47:04 | PLUMBING PLAN REVIEW |
| | PERMIT: 14030562 |
| | ADD: 1875 PALM BCH LAKES # A09 |
| | CONT: TO BE DETERMINED |
| | TEL: (561)373-3902 / KARI |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY APRIL 14/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET P1.1 PLEASE PROVIDE THE MANUFACTURERS SPEC |
| | SHEETS FOR THE FOLLOWING PLUMBING FIXTURES; |
| | |
| | 1A) TRENCH DRAINS AND IN ACCORDANCE WITH 2010 FBC-P |
| | 412.1 APPROVAL. |
| | TRENCH DRAINS SHALL COMPLY WITH ASME A112.6.3. |
| | |
| | 1B) IT-1 GOOSE NECK W/ 8'-0" VINYL HOSE 2010 FBC-P |
| | 424.6 HOSE-CONNECTED OUTLETS. |
| | FAUCETS AND FIXTURE FITTINGS WITH HOSE-CONNECTED |
| | OUTLETS SHALL CONFORM TO ASME A112.18.3M OR CSA B125. |
| | |
| | 1C) OXY 1-3 HJC VENDOR CUT SHEETS 2010 FBC-P 1201.1 |
| | SCOPE. |
| | THE PROVISIONS OF THIS CHAPTER SHALL GOVERN THE DESIGN |
| | AND INSTALLATION OF PIPING AND STORAGE SYSTEMS FOR |
| | NONFLAMMABLE MEDICAL GAS SYSTEMS AND NONMEDICAL OXYGEN |
| | SYSTEMS. ALL MAINTENANCE AND OPERATIONS OF SUCH SYSTEMS |
| | SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | PLEASE PROVIDE A MED-GAS PLAN FOR THE OXYGEN UNDER A |
| | SEPERATE PERMIT. DETAILS CAN BE ONTHIS PLAN. REQUIRES A |
| | DIFFERNT PERMIT, BECAUSE OF THE INSPECTION CODES ARE |
| | DIFFERENT FROM THE PLUMBING. |
| | |
| | 1D) SB1, SB2 & SB3 SCAVENGER VACCUUM UNIT , DROPS AND |
| | WET TABLE OUTLETS. PLEASE PROVIDE THE MANUFACTURERS CUT |
| | SHEETS ON THEASE PRODUCTS. 2010 FBC-P 713.4 OR 713.5. |
| | THE PLANS DO NOT PROVIDE A CLEAR VIEW OF THE SCAVENGER |
| | VACCUUM UNIT AND PIPING LAYOUT NOR DOES THE PLANS |
| | INDICATE WHERE THE VENT ON THE PUMP IS GOING TO VENT |
| | TO. THE EXHAUSTS FROM A VACUUM PUMP SERVING A VACUUM |
| | (FLUID SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO |
| | OPEN AIR ABOVE THE ROOF. 713.6. |
| | |
| | 2) SHEET P0.1 HEADING PB-7 2 /250 OXYGEN CYLINDERS |
| | PROVIDE DETAIL FOR SECURING TO WALL AND FOR THE |
| | MANIFOLD. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |