| Date |
Text |
| 2014-03-31 11:41:10 | PERMIT #14030562 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FAIL COMMENT: ENGINEERED FIRE ALARM AND FIRE SPRINKLER |
| | CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL |
| | BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN |
| | ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP |
| | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION |
| | DOCUMENTS) FOR A SUB-PERMIT. |
| | |
| | PROVISO COMMENTS: |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED BY EMAIL ([email protected]) |
| | ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A |
| | LOCK/UNLOCK INDICATOR. (REQUIRED ON ALL ENTRY DOORS, |
| | I.E., DOUBLE DOORS SHOULD HAVE 2 INDICATORS.) |
| | |
| | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH |
| | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL |
| | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| | SPACED NOT MORE THAN 15 FEET ON CENTER. |
| | |
| | PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN |
| | STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE |
| | MAINTAINED AT ALL TIMES. |
| | |
| | AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY |
| | EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL |
| | EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED |
| | WITH RESPECT TO THEIR DUTIES UNDER THE PLAN. |
| | |
| | EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED |
| | IN THE USE OF PORTABLE FIRE EXTINGUISHERS. |
| | |
| | SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE |
| | FIRE ALARM AND SPRINKLER SYSTEM. |
| | |
| | WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT |
| | SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED |
| | AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE |
| | MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM |
| | SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD |
| | INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY |
| | BE NEEDED. |
| | |