| 2014-04-17 15:24:02 | 14030562 |
| | 1875 PALM BEACH LAKES BLVD. #A09 |
| | PET?S MART |
| | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN |
| | DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22 |
| | |
| | PROVIDE DEDICATED EQUIPMENT SPACES WITH SAFE WORKING |
| | CLEARANCE AND DIMENSIONS FOR THE SWITCH BOARDS AND |
| | PANEL BOARDS. 110.26 |
| | |
| | PROVIDE SPECIFICATIONS AND LISTING FOR HILL PHOENIX |
| | ELECTRICAL EQUIPMENT SPECIFIED. VERIFY THIS EQUIPMENT |
| | IS MARKED AS SUITABLE FOR USE AS SERVICE EQUIPMENT. NEC |
| | 110.3, 230.66 |
| | |
| | PROVIDE DETAILS OF ALL ELECTRICAL SERVICES PROPOSED FOR |
| | THIS BUILDING (BUILDING ?A?). THE MASTER PLAN LIMITS |
| | THE NUMBER OF MAIN DISCONNECTS TO FOUR WHICH MUST BE |
| | GROUPED IN ONE LOCATION. NEC 230.2; 230.40; 230.70; |
| | 230.71 |
| | |
| | PROVIDE CALCULATIONS CLARIFYING THE SELECTION OF |
| | PRIMARY AND SECONDARY PROTECTION FOR TRANSFORMER ?T?. |
| | NEC 450.3(B) |
| | |
| | SHOW LOCATION OF THE MAIN DISCONNECTS FOR THE PANELS |
| | FED FROM TRANSFORMER (T1). VERIFY DISCONNECTS ARE |
| | GROUPED. VERIFY THE TAP CONDUCTORS ARE THE APPROPRIATE |
| | LENGTH. NEC 240.21, 450.3 (B); 240.4(F); 240.21(C) |
| | |
| | PANEL ?LA? REQUIRES A LARGER FEEDER. NEC 240.4; 240.6; |
| | T. 310.16 |
| | |
| | PROVIDE SPECIFICATIONS AND LISTING FOR THE 400 AMP |
| | SERVICE RATED MAIN DISCONNECT. NEC 110.3 |
| | |
| | PROVIDE SPECIFICATIONS FOR THE GENERATOR TRANSFER |
| | SWITCH. INCLUDE A GENERATOR DISCONNECT, LOAD |
| | CALCULATION, LOCATION SIGNAGE, GROUNDING AND FEEDER |
| | SIZE. NEC 215.5; 445.13; 445.18; 702.5; 702.8; 702.10 |
| | |
| | PROVIDE SPECIFICATIONS AND LISTING FOR THE X-RAY |
| | EQUIPMENT AND DISCONNECT. NEC 110.3 |
| | |
| | PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF ROOF TOP |
| | EQUIPMENT. NEC 210.8; 210.63 |
| | |
| | SHOW THE LIGHTING BRANCH CIRCUITS ON THE LIGHTING FLOOR |
| | PLAN. NEC 210.11 |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING |
| | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| | REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; 505.5.3; T |
| | 505.5.3 |
| | |
| | PROVIDE OR CONFIRM THAT THE INTERIOR AND EXTERIOR |
| | LIGHTING CONTROLS PROVIDED ARE IN ACCORDANCE WITH THE |
| | FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL |
| | BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME |
| | SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST |
| | 10 HOURS. FBC ENERGY CONSERVATION 505.2 |
| | |
| | PROVIDE LIGHTING CONTROLS ON THE SIGN CIRCUIT. |
| | AUTOMATIC CONTROLS SHALL BE CAPABLE OF RETAINING |
| | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER |
| | FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY |
| | CONSERVATION 505.2 |
| | |
| | CONDUCTORS FOR DATA AND COMMUNICATIONS SYSTEMS LOCATED |
| | AT OR BELOW GRADE MUST BE LISTED AS SUITABLE FOR DAMP |
| | OR WET LOCATIONS. NEC 110.3, 110.8, |
| | |
| | |
| | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE |
| | ALARM SYSTEMS, SECURITY, VOICE, DATA SYSTEMS, AND |
| | GENERATOR. |
| | |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS REVIEW |
| | 561-373-3701 |
| | |
| | |