| Plan Review Notes For Permit 14030543 |
| Permit Number |
14030543 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-18 09:12:58 | SEE BUILDING PLAN REVIEW COMMENTS ON QUALITY OF PLAN, | | | ADDITIONALLY, ASSURE THE FOLLOWING WILL BE ADHERED TO | | | BY NOTATION UPON PLAN: | | | NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES | | | SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE | | | BRANCH CIRCUITS. | | | NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. | | | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO | | | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM, IF THERE IS AN ATTACHED | | | GARAGE OR FOSSIL FUEL BURNING APPLIANCES. | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|