| Plan Review Notes For Permit 14030531 |
| Permit Number |
14030531 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-26 13:40:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | | | | 1. BOND BREAK REQUIRED PER FBC 2010 RESIDENTIAL | | | 703.6.3. PROVIDE A SPECIFICATION OR DETAIL. | | | | | | 2. IMPACT PROTECTION REQUIRED FOR GLAZING,FBC1609.1.4, | | | FBC R 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF | | | SHUTTERS ARE USED, COMPLETE THE SAMPLE INSTALLATION | | | SCHEDULE (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITY | | | OFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PD | | | F) | | | | | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4, | | | PROVIDE CALCULATIONS. | | | | | | 3. PROVIDE A DETAIL OR SPECIFICATION WHICH SHOWS HOW | | | THIS INSTALLATION WILL COMPLY WITH FBC 2010 R704, | | | INSPECTION FOR TERMITES. |
|