| 2014-04-05 12:01:28 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE RETURN DUCT IS NOT SHOWN ON THE MECHANICAL PLANS | | | FOR THE RETURN GRILLS SHOWN IN THE MASTER BEDROOM AND | | | THE LIVING ROOM. CITY AMENDMENTS 107.2.1 | | | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT | | | MATCHES THE SIZING CALCULATIONS. CITY AMENDMENTS | | | 107.2.1 | | | | | | 3) THE 6 X 12 TRANSFER GRILLS SPECIFIED FOR BEDROOMS | | | ONE AND TWO ARE TOO SMALL. FBCR M1602.4 REQUIRES 50 | | | SQIN OF GRILL AREA FOR TO 100 CFMS OF SUPPLY AIR. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|