| Plan Review Notes For Permit 14030509 |
| Permit Number |
14030509 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-04-21 17:01:56 | NO ELECTRICAL DATA PROVIDED.. THE ELECTRICAL SPECS | | | SUBMITTED ARE FOR A MANUFACTURED TRAILER THAT IS BEING | | | DELIVERED TO THE SITE ALREADY INSPECTED BY THE STATE OF | | | FLORIDA. THE ELECTRICAL DATA REQUIRED IS A SERVICE | | | RISER DIAGRAM WITH LOAD CALCS; A SITE PLAN INDICATING | | | WHERE THE POWER FOR THIS/THESE UNITS IS BEING OBTAINED | | | FROM AND A DESCRIPTION OF ALL THIS IS GOING TO GET PUT | | | TOGETHER. |
|