Plan Review Notes
Plan Review Notes For Permit 14030501
Permit Number 14030501
Review Stop E
Sequence Number 2
Notes
Date Text
2014-03-18 12:50:35THE FOLLOWING CONDITIONS/RESTRICTIONS WERE APPLIED TO
 THE APPROVED PERMIT.
 1. EVERY CIRCUIT W/A SHARED NEUTRAL SHALL COMPLY W/NEC
 210.4(B)
 2. AS PER NEC TABLE 250.122 THE GEC FOR CIRCUIT 4/6 OF
 PANEL TH1 SHALL BE #10CU
 3. TRANSFORMERS SHALL BE GROUNDED AS PER NEC ARTICLE
 250
 4. ALL LOW VOLTAGE WIRE SHALL BE LISTED FOR THE
 APPLICATION
 5. ALL AUXILIARY AUDIO SYSTEMS SHALL BE MUTED BY FACP
 IN THE EVENT OF AN ALARM
  