| Plan Review Notes For Permit 14030501 |
| Permit Number |
14030501 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-03-18 12:50:35 | THE FOLLOWING CONDITIONS/RESTRICTIONS WERE APPLIED TO | | | THE APPROVED PERMIT. | | | 1. EVERY CIRCUIT W/A SHARED NEUTRAL SHALL COMPLY W/NEC | | | 210.4(B) | | | 2. AS PER NEC TABLE 250.122 THE GEC FOR CIRCUIT 4/6 OF | | | PANEL TH1 SHALL BE #10CU | | | 3. TRANSFORMERS SHALL BE GROUNDED AS PER NEC ARTICLE | | | 250 | | | 4. ALL LOW VOLTAGE WIRE SHALL BE LISTED FOR THE | | | APPLICATION | | | 5. ALL AUXILIARY AUDIO SYSTEMS SHALL BE MUTED BY FACP | | | IN THE EVENT OF AN ALARM | | | |
|