Plan Review Notes
Plan Review Notes For Permit 14030485
Permit Number 14030485
Review Stop P
Sequence Number 1
Notes
Date Text
2014-03-13 06:31:10PLUMBING PROVISO:
 2010 FBC-P 1003.5.3 INLET AND OUTLET PIPING.
 THE INLET INVERT SHALL DISCHARGE A MINIMUM 21/2 INCHES
 ABOVE THE LIQUID
 LEVEL LINE AND THE OUTLET PIPE SHALL HAVE A TEE WITH A
 MINIMUM DIAMETER OF
 4 INCHES THAT EXTENDS TO WITHIN 8 INCHES OF THE BOTTOM
 OF THE TANK. THE
 TEE SHALL BE INSTALLED WITH THE RUN IN THE VERTICAL
 DIRECTION.