| Plan Review Notes For Permit 14030477 |
| Permit Number |
14030477 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-21 14:14:32 | SCOPE OF WORK NOT CLEARLY DEFINED. NEED WRITTEN SCOPE | | | OF WORK DEFINING CHANGES. SCOPE HAS GONE FROM 5 TENANT | | | SPACES TO 4. | | | | | | NEED ALL PANEL SCHEDULES FOR ALL SERVICES. | | | | | | SPECS ON GENERATOR, TRANSFER SWITCH, AND RELATED LOAD | | | CALCULATIONS. | | | | | | RISER INDICATES 1000AMP FUSIBLE DISCONNECT. NEC 230.95 | | | GROUNDFAULT PROTECTION OF EQUIPMENT SHALL BE PROVIDED | | | FOR SOLIDLY GROUNDED WYE ELECTRIC SERVICES OF MORE THAN | | | 150 VOLTS TO GROUND BUT NOT EXCEEDING 600 VOLTS | | | PHASE-TO-PHASE FOR EACH SERVICE DISCONNECT RATED 1000 | | | AMPERES OR MORE. | | | | | | E.A.S. LV CABLES INSTALLED IN RACEWAYS UNDERGROUND TO | | | BE RATED FOR WET LOCATION PER NEC 300.5(B) | | | | | | | | | | | | |
|