| 2014-03-18 13:54:56 | THIS APPLICATION FOR PERMIT CAME UP FOR REVIEW AND THE | | | FOLLOWING DEFICIENCIES WERE NOTED: | | | 1. PROVIDE A REASONABLE VALUATION BASED ON THE COST OF | | | THE WORK INCLUSIVE OF LABOR AND MATERIALS REGARDLESS OF | | | FEES CHARGED. | | | 2. AS PER THE FBC 907.1.2 YOUR SUBMITTAL IS MISSING THE | | | REQUIRED VOLTAGE DROP CALCULATIONS AND THE LOCATION OF | | | THE PRIMARY POWER SOURCE. | | | 3. PROVIDE AN INDICATION AS TO WHAT THE CK ROOM IS. | | | | | | IF YOU HAVE ANY QUESTIONS WITH REGARDS TO THIS REVIEW, | | | PLEASE DO NOT HESITATE TO CONTACT ME: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER CITY OF WEST | | | PALM BEACH | | | PH: (561) 805-6718 |
|