| Date |
Text |
| 2014-03-27 16:11:30 | 1855 PALM BEACH LAKES BOULEVARD - BUILDING B2 |
| | PERMIT #14030343 |
| | MASTER #13090100 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE CURRENT LAYOUT WILL CAUSE MASS CONFUSION TO |
| | EMERGENCY RESPONDERS BECAUSE THE SPRINKLER RISER |
| | (LOCATED ADJACENT TO THE ELECTRICAL CLOSET AT COLUMN |
| | LINE BII1) PROTECTS TENANT SPACE B11 BUT THEN SKIPS |
| | TENANT SPACES B8, B9 AND B9 TO THE SOUTH AND THEN |
| | PROTECTS TENANT SPACES B1-B7 TO SOUTH. RECOMMEND |
| | EXTENDING THE 6-INCH UNDERGROUND FIRE LINE SUPPLYING |
| | THE FIRE HYDRANT OUTSIDE THE B4 TENANT SPACE AND |
| | PROVIDING A SPRINKLER RISER IN THIS LOCATION TO PROTECT |
| | TENANTS B1-B7. THE SPRINKLER RISER IN B10 CAN THEN |
| | PROTECT TENANTS B8-B11 AND THE LANDLORD SPACES. |
| | |
| | PROVIDE A WALL PIV AND FENCING AROUND THE SPRINKLER |
| | RISERS TO PREVENT THE INDIVIDUAL TENANTS FROM |
| | ATTEMPTING TO CONTROL THE LANDLORD OWNED SPRINKLER |
| | SYSTEMS PROTECTING THE BUILDINGS. |
| | |
| | THE SPRINKLER RISERS AND FDC CONNECTIONS SHALL BE |
| | PROVIDED WITH PERMANENT WEATHERPROOF SIGNAGE INDICATING |
| | WHICH BUILDING THEY ARE PROTECTING. |
| | |
| | PROVIDE LOCKING KNOX CAPS ON THE FIRE DEPARTMENT |
| | CONNECTIONS. |
| | |
| | MINIMUM 1-INCH OUTLETS SHALL BE PROVIDED ON BRANCH |
| | LINES TO ACCOMMODATE TENANT FITOUTS THAT MAY UTILIZE |
| | LAY-IN CEILINGS. |
| | |
| | PROVIDE PERMANENT WEATHERPROOF SIGNAGE INDICATING WHAT |
| | PORTIONS OF THE BUILDINGS THE RISERS AND FDCS PROTECT. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |