2014-03-31 12:32:05BUILDING PLAN REVIEW
 PERMIT: 14030339
 ADD: 6901 OKEECHOBEE BLVD # C-14
 CONT: NOWAK CONSTRUCTION
 TEL: (561)779-9577
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MARCH 31/ 2014
 ACTION: DENIED
  
 2ND REVIEW ALL NOTES STAND. THE PLANS ARE NOT SIGNED
 AND SEALED, IN THE TITLE BLOCK PLANS STATE THEY ARE THE
 DESIGN OF R. GARY GLUECK. HAND WRITTEN NOTES ARE ALL
 OVER TTHE PLANS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003 ARCHITECTS
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHETECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003
  
 61G1-16.003 USE OF SEAL. EFFECTIVE 04/18/2000
 THE PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT
 OR INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL
 OR INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC
 RECORD AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS
 OR HIS CORPORATION. A CORPORATE SEAL ALONE IS
 INSUFFICIENT. DOCUMENTS SHALL BE SIGNED PERSONALLY AND
 SEALED BY THE RESPONSIBLE ARCHITECT OR INTERIOR
 DESIGNER. FINAL OFFICIAL RECORD DOCUMENTS (NOT
 TRACINGS, ETC.) SHALL BE SO SIGNED. THE SIGNING AND
 SEALING OF THE SPECIFICATION INDEX SHEETS SHALL BE
 CONSIDERED ADEQUATE. ALL DRAWING SHEETS AND PAGES SHALL
 BE SO SIGNED AND SEALED. AN ARCHITECT OR INTERIOR
 DESIGNER SHALL NOT AFFIX, OR PERMIT TO BE AFFIXED, HIS
 SEAL OR NAME TO ANY PLAN, SPECIFICATIONS, DRAWINGS, OR
 OTHER RELATED DOCUMENT WHICH WAS NOT PREPARED BY HIM OR
 UNDER HIS RESPONSIBLE SUPERVISING CONTROL AS PROVIDED
 IN RULE CHAPTER 61G1-23, F.A.C. AN ARCHITECT OR
 INTERIOR DESIGNER SHALL NOT USE HIS SEAL OR DO ANY
 OTHER ACT AS AN ARCHITECT OR INTERIOR DESIGNER UNLESS
 HOLDING AT THE TIME A CERTIFICATE OF REGISTRATION AND
 ALL REQUIRED RENEWALS THEREOF.
  
  
  
 1) COVER SHEET, SHEET A1, UNDER THE HEADING PROJECT
 DATA:
 UNDER THE HEADING THE BUILDING TYPE IS LISTED AS A TYPE
 II-B, UNDER THE CONSTRUCTION TYPE THE STRUCTURE IS
 LISTED AS A BUILDING
 TYPE IIA, SPRINKLERED UNPROTECTED. PLEASE REFER TO THE
 2010 FBC-B TABLE 601 A BUILDING CAN NOT BE DECLARED
 BOTH TYPE II A & B, THEY ARE EITHER DESIGNED WITH 1 HR
 FIRE PROTECTION (A) OR UNPROTECTED- NO FIRE RATING OF
 STRUCTURAL MEMBERS (B).
  
 2) COVERSHEET, SHEET A1 DETAIL # 9 TYPICAL FIXTURE
 CLEARANCES INDICATES A 48 X 60 INCH CLEAR FLOOR SPACE
 IN FRONT OF THE WATER CLOSET, PLEASE REFER TO THE 2010
 FBC- ACCESSIBILITY CODE SECTION 604.3 CLEARANCE,
 604.3.1 SIZE & 604.3.2 FOR ALLOWABLE OVERLAP ALSO SEE
 FIGURE 604.3.1.
  
 3) SHEET A2 FLOOR PLAN:
  
 3A) INDICATES THE USE OF A DOUBLE DRINKING FOUNTAIN,
 THE PLANS DO NOT PROVIDE A DETAIL INDICATING COMPLIANCE
 WITH 2010 FL ACCESSIBILITY CODE
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
  
 3B) THIS SHEET ALSO INDICATES A SIDE APPROACH TO THE
 DRINKING FOUNTAIN, PLEASE REVIEW 2010 FL ACCESSIBILITY
 CODE, 602.2 CLEAR FLOOR SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3C) THE 2 NEW DOORS IN THE NEW WALLS DOES NOT PROVIDE
 THE WIDTH OF THE DOORS NOR THE TYPE OF HARDWARE TO BE
 INSTALLED IN THESE DOORS,
 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1008.1.1 SIZE OF
 DOOR & 1008.1.9.3 LOCKS AND LATCHES.
  
 3D) EISTING EGRESS DOORS APPEAR TO HAVE EXISITNG DEAD
 BOLTS PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1008.1.9.3
 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT
 LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN
 PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR
 DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED
 LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED:
  
 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS
 LOCKED;
  
 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE
 EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS
 DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE
 SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND; AND
  
 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS
 REVOCABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  