| Plan Review Notes For Permit 14030339 |
| Permit Number |
14030339 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-03-12 18:37:55 | FAILED 1ST ELECTRICAL REVIEW FOR THE FOLLOWING: | | | 1. SHALL PROVIDE A PANEL SCHEDULE WITH CIRCUIT | | | DESIGNATIONS FOR PREMISES. | | | 2. SHALL SUBMIT AN ELECTRICAL RISER DIAGRAM | | | 3. SHALL PROVIDE ELECTRICAL LOAD CALCS. | | | 4. INCLUDE IN THE PANEL SCHEDULE AND LOAD CALCS THE A/C | | | & HEATING LOADS | | | THE SCOPE OF THIS EXCLUDES ANY LOW VOLTAGE WORK SUCH AS | | | ANY CCTV, SECURITY SYSTEM OR AUDIO | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | |
|